Festo CPV-D102 Elektronics Manual page 121

With field bus direct connection
Table of Contents

Advertisement

5. Diagnosis CPV−CS02 (ABB CS31)
LED
Colour
PL
off
PL
green
flashes fast
PL
green
flashes slowly
PL
green
lights up
Tab. 5/3:
Fault diagnosis with the green LED PL
Festo P.BE−CPV−DI02−E N en 0704NH
Fault diagnosis with the LED PL
The green LED PL (Power Load") indicates faults in the load
voltage supply.
Operating status
Load voltage for valves/outputs
not applied
Load voltage of CP valves of the
CPV Direct . 20.4 V
Load voltage of the CP valves/
outputs in the CPI extension string
. 20.4 V
Load voltage for CP valves/
outputs is applied
Load voltage faults are always displayed with the LED PL
(irrespective of the diagnostic mode set).
Fault treatment
Check load voltage supply
·
(pin 2)
Check load voltage supply of
·
the CPI extension string (pin 2)
5−5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cpv-di02Profibud-dpCpv-cs02Abb cs31Profibus-dpCpv-di02 profibus-dp series ... Show all

Table of Contents