Emerson Rosemount 5900S Reference Manual page 199

Radar level gauge
Hide thumbs Also See for Rosemount 5900S:
Table of Contents

Advertisement

Reference Manual
00809-0100-5900
3. Locate the write protection switch. It is the second switch (2) marked P.
4. To write protect the level gauge, move switch P to the upper position.
5. Check that contact surfaces on the housing and cover are clean. Replace the cover
6.2.8
Logging measurement data using TankMaster
The Rosemount 5900S supports logging of diagnostic registers. This function is useful for
verifying that the gauge works properly. The logging function can be accessed by using
the Rosemount TankMaster WinSetup program.
Procedure
1. Start the Rosemount TankMaster WinSetup program.
2. In the TankMaster WinSetup workspace window, select the device icon.
Rosemount 5900S Radar Level Gauge
and tighten the screws. Make sure that the cover is fully engaged to meet
explosion-proof requirements and to prevent water from entering the terminal
compartment.
Note
Ensure that O-rings and seats are in good condition prior to mounting the cover in
order to maintain the specified level of ingress protection.
Service and troubleshooting
September 2019
199