LPG setup using Rosemount
This section describes how to configure the Rosemount 5900S for LPG measurements by
using the Rosemount TankMaster configuration tool.
Prerequisites
In the following description it is assumed that the Rosemount 5900S with LPG/LNG
Antenna is installed on the tank, and a basic configuration is performed as described in the
Rosemount Tank Gauging
Configure the vapor pressure sensor
Prerequisites
Ensure that a Vapor Pressure source device is up and running.
Procedure
1. Verify that the tank is empty and the tank atmosphere contains air only.
2. Check that the ball valve (optional) on the gauge is open.
3. Configure a Vapor Pressure source device. Open the ATD Properties window and
Rosemount 5900S Radar Level Gauge
System Configuration
select the Advanced Parameter Source Configuration tab.
This tab lets you map tank parameters such as Vapor Pressure to source devices
connected to the Tankbus.
TankMaster
Manual.
Configuration
September 2019
117