Service and troubleshooting
September 2019
Table 6-2: Device Status Messages
Message
Invalid Measurement
Write Protected
Default Database
Simulation Active
SIL Mode Enabled
FF Out of Service
RM Reprogramming In Progress
6.3.2
Warning messages
Table 6-3
Rosemount 2410 Tank Hub and in the Rosemount TankMaster program. You also have the
option to view Input register 1004 for an overview of active device warnings. Warnings are
less serious than errors.
For each warning message that may appear, detailed information can be found in Input
registers 6100 to 6130 as shown in
Table 6-3: Warning Messages
Message
RAM warning
FPROM warning
HREG warning
208
(continued)
Description
The level gauge indicates that
measurement is invalid. This may be
caused by an actual measurement
problem or some other error
indication.
The configuration registers are write
protected.
All configuration registers are set to
default values.
The Rosemount 5900S is in simulation
mode.
The level gauge operates in SIL mode.
The level gauge is set to Out of Service
mode in order to allow service or
configuration.
New software is downloaded to the
Rosemount 5900S
shows a list of Warning messages that may appear on the integral display of the
Description
Input register no. 6100.
Bit 0: DSP Stack
Bit 1: DSP RAM low
Input register no. 6102.
Input register no. 6104.
Bit 0: DSP Factory holding registers
Action
Check Error Messages, Warning
Messages and Measurement Status for
details.
Do one of the following:
1. Use the Lock/Unlock function to
turn off the software write
protection.
2. Change position of the Write
Protection switch to OFF.
Ensure that device calibration is valid.
Reset Rosemount 5900S simulation
mode.
Ensure that the gauge is properly
configured for SIL application.
Ensure that mode is changed back to
In Service when the gauge is back in
operation.
Verify Rosemount 5900S operation
when reprogramming is finished.
Table
6-3.
Action
Contact Emerson Automation
Solutions /Rosemount Tank Gauging
service department.
Load default database and restart the
Rosemount 5900S. Contact Emerson
Automation Solutions/Rosemount
Tank Gauging service department if
the problem persists.
Reference Manual
00809-0100-5900
Reference Manual