Table C-3: Definitions of Analog Input Function Block System Parameters
Index Number Parameter
01
ST_REV
02
TAG_DESC
03
STRATEGY
04
ALERT_KEY
05
MODE_BLK
06
BLOCK_ERR
07
PV
08
OUT
09
SIMULATE
10
XD_SCALE
11
OUT_SCALE
12
GRANT_DENY
13
IO_OPTS
14
STATUS_OPTS
15
CHANNEL
16
L_TYPE
17
LOW_CUT
18
PV_FTIME
Rosemount 5900S Radar Level Gauge
Units
Description
None
The revision level of the static data associated with the function
block. The revision value will be incremented each time a static
parameter value in the block is changed.
None
The user description of the intended application of the block.
None
The strategy field can be used to identify grouping of blocks. This
data is not checked or processed by the block.
None
The identification number of the plant unit. This information may
be used in the host for sorting alarms, etc.
None
The actual, target, permitted, and normal modes of the block.
Target: The mode to "go to"
Actual: The mode the "block is currently in"
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
None
This parameter reflects the error status associated with the
hardware or software components associated with a block. It is a bit
string, so that multiple errors may be shown.
EU of
The process variable used in block execution.
XD_SCALE
EU of
The block output value and status.
OUT_SCALE
None
A group of data that contains the current transducer value and
status, the simulated transducer value and status, and the enable/
disable bit.
None
The high and low scale values, engineering units code, and number
of digits to the right of the decimal point associated with the
channel input value.
None
The high and low scale values, engineering units code, and number
of digits to the right of the decimal point associated with OUT.
None
Options for controlling access of host computers and local control
panels to operating, tuning, and alarm parameters of the block. Not
used by device.
None
Allows the selection of input/output options used to alter the PV.
Low cutoff enabled is the only selectable option.
None
Allows you to select option for status handling and processing.
None
The CHANNEL value is used to select the measurement value.
You must configure the CHANNEL parameter before you can
configure the XD_SCALE parameter.
None
Linearization type. Determines whether the field value is used
directly (Direct) or is converted linearly (Indirect).
%
If percentage value of transducer input fails below this, PV = 0.
Seconds
The time constant of the first-order PV filter. It is the time required
for a 63 percent change in the IN value.
F
Fieldbus Block Information
OUNDATION
September 2019
275