Lpg Configuration - Emerson Rosemount 5900S Reference Manual

Radar level gauge
Hide thumbs Also See for Rosemount 5900S:
Table of Contents

Advertisement

Configuration
September 2019
4.6

LPG configuration

4.6.1
Preparations
Prerequisites
Before starting configuration of the Rosemount
that all mechanical installations are made according to instructions, and all external
sensors such as pressure and temperature sensors are properly connected.
For Rosemount 5900S with F
using DeltaV / AMS Device
Highly pressurized vapor above the product surface affects the propagation speed of
microwaves. The Rosemount 5900S level gauge is able to compensate for this, thus
avoiding deviations in measured level due to the vapor.
When the gauge is installed on the empty tank, calibrate the gauge and configure for LPG
measurements.
To install a Rosemount 5900S for LPG measurements perform the following major steps:
Procedure
1. Install the tank and the Rosemount 5900S level gauge in Rosemount TankMaster
2. Install the Rosemount 5900S gauge on the still-pipe. Measure the exact distance to
3. Configure the Rosemount 5900S according to the standard procedure for a
4. Configure the vapor pressure sensor.
5. Set Correction Method to Air Correction Only.
6. Calibrate the Rosemount 5900S.
7. Configure the Verification Pin.
8. Verify position of Verification Pin.
9. Set up the Correction Method that applies to the particular type of product in the
116
OUNDATION
Manager.
WinSetup as described in the Rosemount Tank Gauging
Manual. Ensure that the appropriate tank and device types are selected, and the
temperature and pressure sensors are properly configured. Check that the gauge
communicates with the TankMaster PC.
the Verification Pin.
Rosemount 5900S level gauge (see the Rosemount Tank Gauging
Configuration
Manual). Rosemount TankMaster Winsetup is the recommended
configuration tool.
tank.
The LPG installation procedure using Rosemount TankMaster Winsetup is described
in section
LPG setup using Rosemount
5900S for LPG measurements, ensure
Fieldbus the LPG Setup is described in
System Configuration
TankMaster.
Reference Manual
00809-0100-5900
LPG Setup
System
Reference Manual