00809-0100-5900
Table 6-1: Troubleshooting Chart for the Rosemount 5900S
Symptom
No level measurement
Rosemount 5900S Radar Level Gauge
Possible cause
Incorrect configuration of
Rosemount 2410 Tank Hub
Connection to Rosemount
2410 Tank Hub
Configuration of
communication protocol
Communication failure
Configuration
Incorrect configuration of
the Rosemount 2460
System Hub's tank database
(continued)
Action
Check the Rosemount 2410 tank database; ensure that
the device is available and mapped to the right tank
In Rosemount TankMaster WinSetup open the
Rosemount 2410 Tank Hub /Tank Database window and
check that the Level Modbus address is equal to the
2410 Level Modbus address in the Rosemount 2460
System Hub's tank database
See the Rosemount Tank Gauging
Configuration Manual
for more information on how to
configure the tank database of the Rosemount 2410.
Check wiring to the Rosemount 2410 Tank Hub
Check the Rosemount 2410 Tank Hub; check the Error
LED or the integral display for information
In the Rosemount TankMaster WinSetup/Protocol Channel
Properties window:
Check that the protocol channel is enabled
Check the protocol channel configuration (port,
parameters, modem)
Check wiring
Check the Modbus communication address for the
Rosemount 5900S. See the Rosemount Tank Gauging
System Configuration Manual
how to setup the Modbus address of a Rosemount
5900S Radar Level Gauge.
Check configuration of the Rosemount 2410 Tank
Hub's tank database
Check configuration of the Rosemount 2460 System
Hub's tank database
Check that the Rosemount 5900S is configured (see
the Rosemount Tank Gauging
Manualfor more information)
Check the Modbus communication address in the
system hub's tank database. In Rosemount TankMaster
WinSetup open the Rosemount 2460/Tank Database
window and check that the 2410 Level Modbus address
in the tank database is equal to the Level Modbus
address in the 2410 tank database.
See the Rosemount Tank Gauging
Configuration Manual
for more information on how to
configure the Rosemount 2460 System Hub's tank
database.
Service and troubleshooting
September 2019
System
for more information on
System Configuration
System
205