Service and troubleshooting
September 2019
6.7

Alerts

The AMS Device Manager lets you view active alerts. The alarm parameters (FD_FAIL_ALM,
FD_OFFSPEC_ALM, FD_MAINT_ALM, and FD_CHECK_ALM) contain information regarding
some of the device errors. Active error conditions are displayed in the FD_xxx_ACTIVE
parameter and can easily be listed by using the Service Tools option in AMS Device
Manager. See
6.7.1
Viewing active alerts in AMS Device Manager
Procedure
1. From the Start menu; open the AMS Device Manager application.
2. Open the View → Device Connection View.
3. Double-click the FF network icon and expand the network node to view the devices.
4. Right-click or double-click the desired gauge icon to open the list of menu options:
5. Select the Service Tools option.
6. In the Navigation Pane select the Alerts option
216
Field diagnostic alerts
for more information on the different alert types.