Service and troubleshooting
September 2019
Table 6-1: Troubleshooting Chart for the Rosemount 5900S
Symptom
No communication with the
Rosemount 5900S Radar
Level Gauge
204
Possible cause
Cables are too long
Hardware failure
Software failure
Rosemount 2180 Field Bus
Modem (FBM)
Connection to Rosemount
2460 System Hub
Incorrect configuration of
Rosemount 2460 System
Hub
(continued)
Action
•
Check that the input voltage on the device terminals is
9 V or more
•
Check the Rosemount 5900S Radar Level Gauge
•
Check the Rosemount 2460 System Hub
•
Check the Rosemount 2180 Field Bus Modem (FBM)
•
Check the communication port on the control room PC
•
Contact Emerson Automation Solutions /Rosemount
Tank Gauging service department
•
Restart the Rosemount 5900S gauge. Use for example
the Restart command in Rosemount TankMaster
WinSetup
•
Restart all devices by disconnecting and connecting the
power supply to the Rosemount 2410 Tank Hub
•
Contact Emerson Automation Solutions /Rosemount
Tank Gauging service department
•
Check that the FBM is connected to the right port on
the control room PC
•
Check that the FBM is connected to the right port on
the Rosemount 2460 System Hub
•
Check that the right field bus port on the Rosemount
2460 System Hub is connected to the Primary bus on
the Rosemount 2410 Tank Hub
•
Check communication port LED:s inside the
Rosemount 2460
•
In the system hub's tank database, check the Modbus
communication addresses of the Rosemount 5900S
and the Rosemount 2410 Tank Hub
•
Check configuration of communication parameters for
the field ports
•
Check that the correct communication channel is
selected
•
See the Rosemount Tank Gauging
Configuration Manual
for more information on how to
configure the Rosemount 2460 System Hub
Reference Manual
00809-0100-5900