Service and troubleshooting
September 2019
6.3.3
Error messages
Table 6-4
Rosemount 2410 Tank Hub and in the Rosemount TankMaster program. You also have the
option to view Input register 1002 for an overview of active device errors.
For each error message that may appear, detailed information can be found in Input
registers 6000 to 6030 as shown in
Table 6-4: Error Messages for the Rosemount 5900S
Message
RAM error
FPROM error
210
shows a list of error messages that may appear on the integral display of the
Description
Input register no. 6000.
A gauge data memory (RAM) error has
been detected during the startup
tests.
Note
This automatically resets the gauge.
Serious RAM problem:
Bit 0: DSP RAM
Bit 1: DSP stack
Bit 2: DSP RAM checksum
Bit 3: DSP RAM low
Input register no. 6002.
An error in the gauge program
memory (FPROM) has been detected
during the startup tests.
Note
This automatically resets the gauge.
Serious FPROM problem:
Bit 0: DSP Boot checksum
Bit 1: DSP Boot version
Bit 2: DSP Application checksum
Bit 3: DSP Application version
Bit 4: FPROM device
Bit 5: FPROM erase
Bit 6: FPROM write
Bit 7: FPROM active block not used
Table
6-4.
Action
Contact Emerson Automation
Solutions /Rosemount Tank Gauging
service department
Reference Manual
00809-0100-5900