Manual Supplement
00809-0400-2410, Rev AA
March 2016
Rosemount
®
Enraf
emulation instruction
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1
Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5
Configuration using the FBM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7
Configuration using the EBM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 14
Advanced information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 23
1.1

Introduction

The purpose of this document is to provide guidelines on how to change from Enraf to
Rosemount equipment by exchanging gauges. When an Enraf gauge is replaced with a
Rosemount gauge, it is necessary to configure the Rosemount 2410 Tank Hub for emulation.
The Rosemount field devices, for example Rosemount 5900 Radar Level Gauge and Rosemount
2240S Temperature Transmitter, are connected to the tank hub using the intrinsically safe
Tankbus as usual. Emulation is done in the tank hub only. Each tank hub can emulate up to 10
tanks (10 separate Enraf gauges).
Figure 1-1. Rosemount Devices Replacing Old Gauges in an Existing Enraf System
Temperature Transmitter
2410 Tank Hub
Rosemount
5900S Radar
Rosemount 2240S
Level Gauge
with sensor
Entis
PLC
CIU
Rosemount 2410
Tank Hub
Rosemount 3051S
Pressure Transmitter

Advertisement

loading
Need help?

Need help?

Do you have a question about the Rosemount 2410 and is the answer not in the manual?

Questions and answers

Summary of Contents for Emerson Rosemount 2410

  • Page 1: Table Of Contents

    Rosemount equipment by exchanging gauges. When an Enraf gauge is replaced with a Rosemount gauge, it is necessary to configure the Rosemount 2410 Tank Hub for emulation. The Rosemount field devices, for example Rosemount 5900 Radar Level Gauge and Rosemount 2240S Temperature Transmitter, are connected to the tank hub using the intrinsically safe Tankbus as usual.
  • Page 2 Stop bits: Baud rate: Selectable 1200 (default)/2400 Enraf gauges for emulation The Rosemount 2410 can emulate Enraf gauges with Type of Instrument (TOI), B or C. Table 1-1. Typical Enraf Devices Devices with GPU protocol 811, 854, 894, 873, 973...
  • Page 3 Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 1.1.2 Rosemount 2410 Tank Hub communication The tank hub has slots for two independent communication boards, primary and secondary ® field bus, for TRL2 Modbus , RS485 Modbus, emulation or wireless communication.
  • Page 4 ® The tank hub supports Emerson ’s wireless technology, which is based on WirelessHART the emerging industry standard for wireless field networks. The Emerson Smart Wireless ™ THUM Adapter acts as a wireless data link between the tank hub and a Smart Wireless Gateway.
  • Page 5: Electrical Installation

    Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 Electrical installation 1.2.1 Rosemount 2410 Tank Hub connections Figure 1-4. Terminal Block in the Explosion-Proof/Flameproof Compartment Primary field bus Secondary field bus Table 1-2. Terminal Assignment for Non-Intrinsically Safe Side Terminal...
  • Page 6 Verify communication with the tank hub through the flashing green LED. 1.2.4 Baud rate The Rosemount 2410 Tank Hub has a pre-configured baud rate (1200) that cannot be changed by the software configuration. The baud rate is controlled by hardware switches on the Enraf communication board. See “Change baud rate”...
  • Page 7: Configuration Using The Fbm

    See the Rosemount Tank Gauging System Configuration Manual (document number 00809-0300-5100) for more information on how to use the TankMaster WinSetup software to configure the Rosemount 2410 Tank Hub. A tank hub where the secondary field bus communicates via WirelessHART, can be configured by wireless communication with a Smart Wireless Gateway.
  • Page 8 Select OK to store the current configuration and close the configuration window. 1.3.2 Install Rosemount 2410 Tank Hub in WinSetup The TankMaster WinSetup wizard is the recommended tool for installing the tank hub. The installation wizard covers basic configuration of the tank hub.
  • Page 9 Manual Supplement Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 From the Device Type drop-down list, select the 2410 Tank Hub option. Type a name in the 2410 HUB Tag field. The 2410 Hub Tag will be used as an identifier for the tank hub in various windows and dialogs.
  • Page 10 Manual Supplement Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 Default Modbus Address is 247 for the tank hub. It is recommended to change it to an address 101-199. Do the following: In the 2410 Tank Hub Communication window select Change Address on Device...
  • Page 11 Manual Supplement Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 When replacing an Enraf gauge with a Rosemount device, the Rosemount device must have the same Enraf address as the replaced one. Set Emulation address for the Rosemount devices (possible Enraf addresses are...
  • Page 12 Manual Supplement Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 In the Gauge Type drop-down list select 811 for gauges such as 811, 854, 894, 873 and 973 (TOI B), or select 813 (TOI C). There are several emulation configuration parameters that can be enabled for specific settings.
  • Page 13 Manual Supplement Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 All Enraf unit types are separately configurable (optional). In the drop-down list for Emulation Units, select desired unit types. Select Apply. 1.3.4 Configure field devices When the tank hub configuration is completed, the Rosemount field devices, for example Rosemount 5900 Radar Level Gauge and Rosemount 2240S Multi-input Temperature Transmitter, must be configured as well.
  • Page 14: Configuration Using The Ebm

    Right click the proper MbMaster icon and select Properties to configure the protocol channel. See the Rosemount Tank Gauging System Configuration Manual (document number 00809-0300-5100) for more information on how to use the TankMaster WinSetup software to configure the Rosemount 2410 Tank Hub. Rosemount 2410 Tank Hub...
  • Page 15 Manual Supplement Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 Select the Communication tab. Set the communication parameters: Port The COM port the EBM will connect to Baud rate 1200 Stop bits Parity None Modem RS-232 Handshaking None Reply timeout...
  • Page 16 00809-0400-2410, Rev AA March 2016 1.4.2 Install Rosemount 2410 Tank Hub in WinSetup The TankMaster WinSetup wizard is the recommended tool for installing the tank hub. The installation wizard covers basic configuration of the tank hub. Perform the following steps to start the installation wizard in TankMaster WinSetup: In the Workspace window select the Device folder.
  • Page 17 Manual Supplement Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 Make sure TankMaster communicates directly with the tank hub and that the proper communication channel is chosen. Default Modbus Address is 247 for the tank hub. It is recommended to change it to an address 101-199.
  • Page 18 Manual Supplement Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 d. The tank hub will not immediately switch from Enraf to Modbus protocol. “Automatic protocol switch mechanism” on page 28 for more information. Select OK to retry. It takes a number of attempts.
  • Page 19 Manual Supplement Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 1.4.3 Configure specific variables for Enraf In the Configuration tab, select Enraf Emulation. When replacing an Enraf gauge with a Rosemount device, the Rosemount device must have the same Enraf address as the replaced one.
  • Page 20 Manual Supplement Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 Tip! In the Tank Database tab, set the Modbus address to the same as the chosen Enraf address for each device. In the Gauge Type drop-down list select 811 for gauges such as 811, 854, 894, 873 and 973 (TOI B), or select 813 (TOI C).
  • Page 21 Manual Supplement Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 There are several emulation configuration parameters that can be enabled for specific settings. Select the desired check boxes to enable specific parameter settings. See parameter description below. Disable Tor C Disable Type of Request (TOR) C response (no response on temperature request).
  • Page 22 Manual Supplement Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 All Enraf unit types are separately configurable (optional). In the drop-down list for Emulation Units, select desired unit types. Select Apply. 1.4.4 Configure field devices When the tank hub configuration is completed the Rosemount field devices, for example Rosemount 5900 Radar Level Gauge and Rosemount 2240S Multi-input Temperature Transmitter, must be configured as well.
  • Page 23: Advanced Information

    Manual Supplement Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 Advanced information 1.5.1 Type of Request (TOR) The Enraf host system can request the following data from the tank hub: Table 1-3. Data Requests Message description Send level alarm status...
  • Page 24 Manual Supplement Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 Table 1-6. Item Settings Requests Message description V0-VF Send or request items: Spot temperatures Send or request items: Average product temperature Send or request items: Average gas temperature Send or request items: Pressure from transmitter 1 (tank...
  • Page 25 Manual Supplement Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 1.5.3 Configuration switches The Enraf communication board is equipped with configuration switches that can be used to change settings such as baud rate and bus gain. Figure 1-6 shows where the switches are located on the communication board.
  • Page 26 Manual Supplement Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 Change Enraf bus gain The Enraf bus gain is by default 10 percent. A long cable and/or high impedance may result in the need to increase gain. Increased gain will improve detection of weaker signals, but also increase the risk of cross talk and EMC disturbance.
  • Page 27 Manual Supplement Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 1.5.4 Troubleshooting Tank hub with two communication boards Verify that communication is working properly, by checking the input registers as described Table 1-9. See Table 1-10 for troubleshooting actions.
  • Page 28 Manual Supplement Rosemount 2410 Tank Hub 00809-0400-2410, Rev AA March 2016 1.5.5 Automatic protocol switch mechanism The tank hub supports a special mechanism to switch protocol from Enraf to Modbus. If the tank hub detects about 20 corrupted messages in a row, the protocol will be switched Figure 1-7.
  • Page 29 March 2016 Contact status If the device is a Type of Instrument C, relay status can also be included in the Enraf contact status. For more info, contact your local Emerson Process Management/ Rosemount Tank Gauging representative. Rosemount 2410 Tank Hub...
  • Page 30 Emerson Process Management Standard Terms and Conditions of Sale can be found at: P.O. Box 20048 www.Emerson.com/en-us/pages/Terms-of-Use.aspx The Emerson logo is a trademark and service mark of Emerson Electric Co. Manama TankMaster, Emerson, THUM Adapter, Rosemount and Rosemount logotype are Bahrain trademarks of Emerson Process Management.