Appendix A Specifications And Reference Data; General - Emerson Rosemount 5900S Reference Manual

Radar level gauge
Hide thumbs Also See for Rosemount 5900S:
Table of Contents

Advertisement

Reference Manual
00809-0100-5900
A
Specifications and reference data
A.1

General

A.1.1
Instrument accuracy
Rosemount 5900S standard
version
Rosemount 5900S 2-in-1 version
Instrument accuracy is under reference conditions. Reference conditions are:
Measurement in test bench at Rosemount Tank Radar AB in Mölnlycke Sweden. Test
bench is calibrated minimum yearly by an accredited laboratory (SP Technical Research
Institute of Sweden. Measuring range is up to 30 m (98 ft). Ambient temperature and
humidity is close to constant during tests. Total uncertainty in test bench is below 0.15
mm (0.006 in.).
A.1.2
Temperature stability
Typically < ± 0.5 mm (0.020 in.) in -40 to +70 °C (-40 to +158 °F)
A.1.3
Fieldbus (standard)
F
OUNDATION
A.1.4
Update time
New measurement every 0.3 s
A.1.5
Repeatability
0.2 mm (0.008 in.)
A.1.6
Maximum level rate
Up to 200 mm/s
A.1.7
Metrology sealing possibility
Yes
(14)
Some level offset may be expected on the secondary unit.
Rosemount 5900S Radar Level Gauge
Fieldbus FISCO (Tankbus)
Specifications and reference data
± 0.5 mm (0.020 in.)
(14)
± 0.5 mm (0.020 in.)
September 2019
223