Configuration
September 2019
4.11.4
Application example
Level value
A Rosemount 5900S Radar Level Gauge measures the product level in a 15 m high tank.
Table 4-7: Analog Input Function Block Configuration for a Rosemount 5900S Level
Gauge
Parameter
L_TYPE
XD_SCALE
OUT_SCALE
CHANNEL
4.11.5
Simulation
To perform lab test of process variables and alerts, you can either change the mode of the
AI block to manual and adjust the output value, or you can enable simulation through the
configuration tool and manually enter a value for the measurement value and its status. In
both cases, you must first set the SIMULATE switch (1) on the field device to the ON
position.
With simulation enabled, the actual measurement value has no impact on the OUT value
or the status.
142
changes to all configurable parameters. The target mode of a block
may be restricted to one or more of the supported modes.
Configured Values
Direct
EU_0=0. EU_100=15. Engineering unit=meter.
EU_0=0. EU_100=15. Engineering unit=meter.
CH1: Level
Reference Manual
00809-0100-5900