Technical Data Of The Current Measuring Modules And The Current / Voltage Measuring Modules - Siemens SIMOCODE pro C System Manual

Industrial controls. motor management and control devices
Table of Contents

Advertisement

Technical data

15.4 Technical data of the current measuring modules and the current / voltage measuring modules

15.4
Technical data of the current measuring modules and the current /
voltage measuring modules
Technical data of the current measuring modules and the 2nd generation current / voltage measuring modules
Mounting
Current setting I
= 0.3 A -
s
4 A; 3 A - 40 A; 10 A - 115 A
(3UF71..-1AA0.-0)
Current
setting I
= 20 A to 200 A
s
(3UF71.3-1.A01-0)
Current
setting I
= 63 A to 630 A
s
(3UF71.4-1BA01-0)
System interface for main
circuit
Current setting I
s
Rated insulation voltage U
pollution degree 3)
Rated operating voltage U
Rated impulse withstand
voltage U
imp
Rated frequency
Type of current
Short circuit
Typical voltage measuring range
Line-to-line voltage / voltage
between lines (e.g.: U
L1L2
Phase voltage (e.g.: U
)
L1
Operating range
Accuracy
at 25°C, 50/60 Hz for the following voltage ranges and limited current ranges
7)
of the voltage measurement
Valid for voltage range:
Line-to-line voltage U
Phase voltage U
in the range 0.85 x 65 V - 1.1 x 400 V
L
of the current measurement
Valid for limited current range:
340
Snap-mounted onto 35-mm standard mounting rail or screw-mounted using additional
push-in lugs
Snap-on mounting onto 35-mm standard mounting rails, screw attachment onto the
mounting plate or direct mounting onto the contactor
Screw attachment to the mounting plate or direct mounting onto the contactor
For connection to a basic unit
3UF7110-1AA01-0: 0.3 A - 4 A
3UF7111-1AA01-0: 3 A - 40 A
3UF7112-1AA01-0: 10 A - 115 A
(at
690 V
i
690 V
e
6 kV
50/60 Hz
Three-phase
Additional short-circuit protection is required in the main circuit
110 V - 690 V
)
65 V to 400 V
0.12 x I
≤ Ie ≤ 10 x I
u
± 1.5%
in the range 0.85 x 110 V - 1.1 x 690 V
L
± 1.5%
3UF7110-1AA01-0: 0.25 A - 8 A
3UF7111-1AA01-0: 2.25 A - 80 A
3UF7112-1AA01-0: 7.5 A - 230 A
3UF7113-1AA01-0: 20 A to 200 A
3UF7113-1BA01-0: 20 A to 200 A
3UF7114-1BA01-0: 63 A to 630 A
o
3UF7113-1AA01-0: 15 A - 400 A
3UF7113-1BA01-0: 15 A - 400 A
3UF7114-1BA01-0: 47 A - 1260 A
System Manual, 05/2019, A5E40507475002A/RS-AD/004
1)