Description of system components
8.3 Operator panel with display
8.3.3.9
Parameters
You can set the following parameters using the operator panel with display:
Parameters
Overload protection → current settings
Current setting Is1
Current setting Is2
Current limits
Monitoring of current limits → trip level I >
(upper limit)
Monitoring of current limits → warning level
I > (upper limit)
Monitoring of current limits → trip level I <
(lower limit)
Monitoring of current limits → warning level
I < (lower limit)
Motor protection → stalled rotor protection
level
Voltage monitoring → voltage limits
Trip level U < (lower limit)
Warning level U < (lower limit)
Cos phi monitoring → Cos phi limits
Trip level cos phi < (lower limit)
Warning level cos phi < (lower limit)
Active power monitoring →
Active power limits
Trip level P > (upper limit)
Warning level P > (upper limit)
Trip level P < (lower limit)
Warning level P < (lower limit)
Ground fault monitoring → Ground fault limits
124
Range
Note
Possible only if a current measuring module is
configured
0.00 - 9,999.00 A
-
0.00 - 9,999.00 A
Possible only in conjunction with the following control
functions:
•
•
•
•
Possible only if a current measuring module is
configured
0 - 1020 % of Is
-
0 - 1020 % of Is
-
0 - 1020 % of Is
-
0 - 1020 % of Is
-
0 - 1020 % of Is
-
Possible only if a current / voltage measuring module
is configured
0 - 2040 V
-
0 - 2040 V
-
Possible only if a current / voltage measuring module
is configured
0 - 100 %
-
0 - 100 %
-
Possible only if a current / voltage measuring module
is configured
0.000 -
-
9999.000 kW
0.000 -
-
9999.000 kW
0.000 -
-
9999.000 kW
0.000 -
-
9999.000 kW
Possible only if a 3UF7510 ground-fault module is
configured
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Dahlander starter
Dahlander reversing starter
Pole-changing starter
Pole-changing reversing starter
SIMOCODE pro