13.1 General information about commissioning and service
Prerequisites
The following prerequisites must be fulfilled for commissioning and servicing:
● SIMOCODE pro is already installed and wired
● The motor is switched off.
Parameterization methods
You can parameterize SIMOCODE pro as follows:
● With the memory module in which the parameters have already been saved from a basic
unit. The memory module is plugged into the system interface. If the memory module is
connected to the system interface and the supply voltage returns to the basic unit, the
basic unit will be automatically parameterized by the memory module. The parameters
can also be downloaded to the basic unit from the memory module by pressing the
TEST / RESET button briefly.
● With the SIMOCODE ES software via serial or USB interface: The PC / PG is connected
to the system interface with a PC cable.
● With an automation system and/or SIMOCODE ES software via PROFIBUS DP. For this
purpose, the PROFIBUS DP cable is connected to the PROFIBUS DP interface of the
basic unit.
● With the initialization module in which the parameters have already been saved from a
basic unit. The initialization module is permanently installed in the switchboard in a Motor
SIMOCODE pro V basic unit into the MCC and the power supply returns to the basic unit,
it will automatically be parameterized by the initialization module.
Commissioning options
There are two commissioning options:
1. Standard case: SIMOCODE pro has not yet been parameterized and has the factory
setting
2. SIMOCODE pro has already been parameterized:
– The parameters have already been loaded into the basic unit.
– The parameters from a previous application still exist. Check whether the parameters
256
Control Center (MCC). If a withdrawable unit with a SIMOCODE pro S or
(e.g. the set current) are correct for the new application. Change these accordingly, if
necessary.
System Manual, 05/2019, A5E40507475002A/RS-AD/004