Commissioning, service, troubleshooting
13.2 Commissioning
Step Description
8
Click the "Connect..." button.
9
Open the "Ethernet parameters" dialog box in the parameter editor
10
Select "Use BOOTP/DHCP" if the IP parameters are obtained from a DHCP server and assigned to the IO Device.
If the DHCP mode is selected, SIMOCODE pro immediately receives an IP address if the DHCP server is available
in the same network. Otherwise the device searches for an IP address. If SIMOCODE pro finds no IP address when
setting up an online connection or during a loading operation, because no DHCP server is available in the network,
SIMOCODE ES assigns the device a temporary IP address. If the DHCP mode is selected, SIMOCODE pro
accepts this temporary address as if it came from a DHCP server. There are two options for deactivating a
temporary IP address again:
Restart the device by means of "Commissioning → Command → Restart/Cold start"
Switch the device off and on again. After the restart, the device runs in the DHCP mode and looks for an IP
address again.
11
Activate/deactivate "Overwrite IP parameters in device" and set the IP address, subnet mask, and router as
appropriate.
The IP parameters are configured with SIMOCODE ES and transferred to the device. In this case, the "Overwrite IP
parameters in device" checkbox must be selected. Choose the IP parameters to match the configuration in the
automation system. If the IP parameters are assigned by the IO controller in the automation system, no setting is
necessary here and the "Overwrite IP parameters in device" checkbox must not be selected
12
Enter the IP address.
13
Activate the checkbox "Use router" if you want to use a router
14
Enter the IP address (gateway) of the router
15
Select the EtherNet/IP device name to match the configuration in the automation system.
16
Activate the "Overwrite device name in device" checkbox if you want to transfer the device name to the device.
17
If necessary, select the "Web server activated" checkbox
18
Select the "Activate NTP synchronization" checkbox if you want to synchronize the unbuffered real-time clock of
SIMOCODE pro V EIP using the NTP procedure.
19
Enter the NTP server address when the "Activate NTP synchronization" checkbox is selected.
20
Enter a value for the time shift: -1440 min to +1440 min (default value: 0 min)
21
Enter a value for the cyclic update interval when the "Activate NTP synchronization" checkbox is selected: 10 to
86400 s (default value: 10 s)
22
Load the data to the basic unit via "Online → Load to device" or click the corresponding button in the menu bar
1)
Note
Initial transfer of device name
The initial transfer of the device name must occur via the SIMOCODE pro system interface,
since the device is not yet accessible via EtherNet/IP due to the missing address settings.
272