15.7
Technical data of the multifunction module
Technical data of the multifunction module
Mounting
Cabinet mounting
Display
Green "READY" LED
System interfaces
Digital module function
Control circuit
Rated insulation voltage U
Rated impulse withstand
voltage U
imp
Inputs (binary)
24 V DC:
•
Cable lengths (single)
Input characteristic
110 V to 240 V AC/DC:
•
Cable lengths (single)
Input characteristic
Relay outputs
Number
•
Function
•
Stipulated short-circuit
•
protection for auxiliary
contacts (relay outputs)
Rated uninterrupted current •
•
Rated switching capacity
•
AC-15
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Snap-mounted onto 35-mm standard mounting rail or screw-mounted using additional
push-in lugs
Minimum distance to be maintained
from cabinet rear wall for series mounting at side: 0 mm
•
from grounded parts at side: 2 mm
•
Continuous light: "Ready for operation"
•
Flashing: "No connection to basic unit"
•
For connection to a SIMOCODE pro S basic unit or an operator panel
300 V (at pollution degree 3)
i
4 kV
4 externally supplied, isolated inputs (24 V DC or 110 V to 240 V AC / DC, depending on
the type), connected to common potential for measuring process signals (e.g. local
control station, key-operated switches, limit switches, ...), freely-assignable to control
functions.
300 m
Type 2 according to EN 61131-2
200 m (cable capacitance 300 nF / km)
—
2 monostable relay outputs (depending on the type)
Isolated NO contacts (NC contact response parameterizable via internal signal
conditioning), relay outputs all with connection to common potential, freely-assignable to
control functions (e.g. line, star or delta contactor or operating state status information).
Fuse links, operating class gL/gG 6 A, quick-response 10 A (IEC 60947-5-1)
•
Miniature circuit breaker 1.6 A, C characteristic (IEC 60947-5-1)
•
Miniature circuit breaker 6 A, C characteristic (I
•
5 A
6 A at max. +50 °C
•
6 A / 24 V AC;
6 A / 120 V AC;
3 A / 230 V AC
15.7 Technical data of the multifunction module
< 500 A)
k
Technical data
357