Technical Data Of The Ground-Fault Module 3Uf7500-1Aa00-0 - Siemens SIMOCODE pro C System Manual

Industrial controls. motor management and control devices
Table of Contents

Advertisement

Technical data
15.6 Technical data of the expansion modules
15.6.7

Technical data of the ground-fault module 3UF7500-1AA00-0

Technical data of the ground-fault module 3UF7500-1AA00-0
Mounting
Display
Green "READY" LED
System interface
Control circuit
Connectable 3UL22 residual current transformer with rated
fault currents I
N
I
≤ 50 % I
ground fault
N
I
≥ 100 % I
ground fault
N
Response delay (conversion time)
Connection
Tightening torque
Connection cross sections
- Connection cross sections, solid:
- Connection cross sections, finely stranded with ferrule:
354
Snap-mounted onto 35 mm standard mounting rail or
screw-mounted using additional push-in lugs
Continuous light: "Ready for operation"
Flashing: "No connection to basic unit"
For connecting to a basic unit, an additional expansion
module, a current measuring module or a current / voltage
measuring module or the operator panel.
0.3 / 0.5 / 1 A
No tripping
Tripping
300 ms to 500 ms, additional delay possible
TORQUE: 7 LB.IN to 10.3 LB.IN 0.8 Nm to 1.2 Nm
2x 0.5 mm
to 2.5 mm
/ 1x 0.5 mm
2
2
2x AWG 20 to 14 / 1x AWG 20 to 12
2x 0.5 mm
to 1.5 mm
/ 1x 0.5 mm
2
2
2x AWG 20 to 16 / 1x AWG 20 to 14
System Manual, 05/2019, A5E40507475002A/RS-AD/004
to 4 mm
2
2
to 2.5 mm
2
2
SIMOCODE pro