Siemens SIMOCODE pro C System Manual page 144

Industrial controls. motor management and control devices
Table of Contents

Advertisement

Description of system components
8.6 Decoupling module (DCM) for 1st generation current/voltage measuring modules (e.g. 3UF711.1AA000)
The tables below show decoupling module requirements for different grounding systems and
system configurations (star systems, delta systems, and single-phase systems):
Star networks:
Table 8- 1
Decoupling module requirements for star networks
Star configuration
4-wire, star, grounded with
low impedance
4-wire, star, grounded with
high impedance
3-wire, star, grounded with
low impedance
3-wire, star, grounded with
high impedance
3-wire, star, with isolated
neutral
144
Network configuration
Decoupling module
required?
No
Yes
No
Yes
Yes
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Note
"TN-S system" according to
IEC 60364
"TN-C system" according to
IEC 60364
"IT system" according to
IEC 60364
SIMOCODE pro

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents