Technical data
15.1 Common technical data
Common technical data
Shock resistance (sine pulse) acc. to IEC 60068-2-27
General
SIMOCODE pro S basic unit and
SIMOCODE pro S multifunction
module assembled on a current
measuring module
SIMOCODE pro V basic unit
assembled on a current / voltage
measuring module
Mounting position
Frequencies
EMC stability according to IEC 60947-1
IEC 60947-1, IEC 60947-5-1,
SN 27095, NE21
DM-F: IEC 61326-3-1
Conducted interference, burst according
to IEC C 61000-4-4
Conducted interference immission, high-
frequency according to IEC 61000-4-6
Conducted interference immission, surge
according to IEC 61000-4-5
Electrostatic discharge, ESD according to
IEC 61000-4-2
4)
Radiated interference immission
according to IEC 61000-4-3
This is a Class A product. This product
can cause radio interference if used in a
domestic environment. Therefore, the
user may need to implement suitable
countermeasures.
Conducted and radiated interference
emission
330
15 g / 11 ms
15 g / 11 ms
15 g / 11 ms
Any
50/60 Hz ± 5 %
Corresponds to degree of severity 3
2 kV (power ports)
Surge suppressor is required for inductive loads.
1 kV (signal ports)
10 V
2 kV (line to earth)
1 kV (line to line)
8 kV (air discharge)
6 kV (contact discharge)
3)
10 V/m
DIN EN 55011/DIN EN 55022 (CISPR11/CISPR22)
(corresponds to Degree of Severity A)
System Manual, 05/2019, A5E40507475002A/RS-AD/004