Siemens SIMOCODE pro C System Manual page 157

Industrial controls. motor management and control devices
Table of Contents

Advertisement

Table 8- 8
Maximum configuration with expansion modules when using an operator panel/operator panel with display, a
2nd generation current/voltage measuring module and a SIMOCODE pro V-PB basic unit with a product
version earlier than E15 / SIMOCODE pro V Modbus basic unit with product version E01
OP
Measur
DM-
ement
F/DM
None/UI
Max. 4 modules
OP
U/I
Max. 4 modules
-
OPD
U/I
-
-
-
1) Max. 1 AM, TM, EM module
Note
Decoupling module
A decoupling module is not necessary for 2nd generation current/voltage measuring
modules.
Configuration instructions for the use of fail-safe expansion modules
In conjunction with DM-F Local and DM-F PROFIsafe fail-safe digital modules, the
expansion modules can be used as follows:
Fail-safe digital
Number of expansion
module
modules
DM-F Local
max. 4
DM-F PROFIsafe
max. 3
Note
Restrictions for the SIMOCODE pro V device series
The restrictions mentioned here apply to the SIMOCODE pro V High Performance device
series with the following product versions:
• SIMOCODE pro V PB: Before E15
• SIMOCODE pro V PN: Before E10
• SIMOCODE pro V MR: Before E03
Devices with the stated product versions or later can be used without restriction with an
operator panel with display and 2nd generation current/voltage measuring modules.
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
8.14 Configuration information for SIMOCODE pro V when using an older basic unit
SIMOCODE pro basic unit
U
= 24 V DC
s
DM
AM
TM
1)
-
Max. 3 modules
1)
-
-
-
-
-
Digital module 2
Description of system components
SIMOCODE pro basic unit
U
= 110-240 V AC/DC
s
EM
DM-
DM
F/DM
-
-
Max. 2 modules
-
Analog module
Temperature
module
AM
TM
EM
1)
Ground-fault
module
157

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents