Siemens SIMOCODE pro C System Manual page 165

Industrial controls. motor management and control devices
Table of Contents

Advertisement

Commands
"Initialization module write protection on" command
All contents of the initialization module are write-protected. This prevents any inadvertent
changes to the contents of the initialization module and any parameter changes to the
connected SIMOCODE pro basic unit. An inadvertent change of parameters for a motor
feeder is prevented. SIMOCODE pro signals successful execution of the command with the
"initialization module write-protected" event.
"Initialization module write protection off" command
With this command, you can remove the write protection of the initialization module.
"Initialization module write protection identification data on" command
The device addressing stored in the initialization module and the I&M data (identification &
maintenance) are write-protected. With this command, you can
● prevent inadvertent changes to the addressing and I&M data for the motor feeder.
● continue to make parameter changes in the initialization module as well as in the
SIMOCODE pro basic unit if the address data and I&M data are identical to the data
already contained in the device when parameters are downloaded.
SIMOCODE pro signals the successful execution of the command with the "initialization
module identification data write-protected" event.
"Initialization module write protection identification data off" command
With this command, you can remove the write protection of the identification data of the
initialization module.
"Clear initialization module data" command:
With this command
● all contents of the initialization module are erased
● The initialization module is reset to the as-delivered state.
SIMOCODE pro signals the successful deletion with the "Initialization module cleared" event.
On startup with an empty initialization module, the basic unit signals
"Fault - parameterization." The "general fault" LED of the basic unit flashes red.
Reparameterization of the device, e.g. with SIMOCODE ES (TIA Portal), writes valid
parameters to the basic unit and the initialization module again. You can then acknowledge
the fault message
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Compartment identification
9.3 Operating compartment identification
165