Siemens SIMOCODE pro C System Manual page 293

Industrial controls. motor management and control devices
Table of Contents

Advertisement

Event
Description
(alphabetical)
Stalled
The torque switch has activated
positioner
before or without the respective
limit switch.
DM-F
The DM-F Local or
feedback
DM-F PROFIsafe has detected a
circuit
fault in the feedback circuit (the
feedback circuit must be closed
as the enabling circuit is switched
on); the "SF" (general fault) LED
on the front of the DM-F Local or
DM-F PROFIsafe is flashing red.
DM-F safety-
The DM-F has tripped the
related
enabling circuit for safety
tripping
reasons.
DM-F test
The enabling circuits of the
requirement
DM-F Local or DM-F PROFIsafe
have not been opened and
closed again within the
configured time period.
DM-F wiring
DM-F module wiring fault (short-
circuit to ground in the sensor
circuit/feedback circuit); the "SF"
(general fault) LED on the front of
the DM-F Local is illuminated
red.
DM-FL actual
The actual configuration of the
and set
DM-F Local does not correspond
configuration
to the parameterized set
different
configuration.
DM-FL
The DM-F Local has detected a
simultaneity
discrepancy error in the
two-channel sensor circuit.
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Troubleshooting
The positioner may be
blocked.
Acknowledge the fault
by releasing with the
"OPEN/CLOSED"
counter command.
Please check the
positioner application
and the limit switches.
Check the wiring of the
feedback circuit
Check the contact
blocks in the feedback
circuit.
The motor cannot be
switched on again until the
enabling circuits of the
DM-F are closed again.
The function of the
enabling circuit relay
contacts can only be
tested when they are
switched. Perform a
function test.
Check the wiring of the
sensor circuits /
feedback circuit
Rectify the fault.
Check whether the
effective configuration of
the DM-F Local
corresponds to the
parameterized set
configuration. Correct the
effective configuration by
changing the DIP switch
settings or adjusting the
set configuration by
means of
parameterization if
required.
Check the switching
elements in the sensor
circuit.
Commissioning, service, troubleshooting
13.4 Troubleshooting
Acknowledgment /
Contactor
fault rectification
control
Counter command
Tripped
"OPEN /
CLOSED!"
Rectify the fault
Tripped
such that the
feedback circuit is
closed.
Acknowledge with
Tripped
"Reset", if auto-
reset is not active.
Please apply the
maintenance
measures
prescribed for this
scenario.
Reset
Tripped
Rectify the fault by
Tripped
opening or closing
the sensor inputs.
Error
No.
1)
12
66
67
293