Commissioning, service, troubleshooting
13.3 Service
Saving parameters from the basic unit to a SIMOCODE ES file
Proceed as follows:
Table 13- 17 Saving parameters to a SIMOCODE ES file
Step
1.
2.
3.
4.
5.
6.
7.
8.
9.
Note
This function will not be available if the TEST / RESET button has been disabled.
Saving parameters from a SIMOCODE ES file into the basic unit
Proceed as follows:
Table 13- 18 Saving parameters from a SIMOCODE ES file into the basic unit
Step
1.
2.
3.
4.
5.
6.
7.
8.
9.
278
Description
Plug the PC cable into the system interface.
Start SIMOCODE ES.
Create a new project via "Create new project".
Switch to the project view.
Go online, e.g. via "Online & Diagnostics" in the project navigator
Open the "Online access" menu in the project navigator and select the suitable interface by
double-clicking it.
Double-click on "Update accessible devices".
Select "Online → Upload device as new station (hardware and software) ...".
Save the project.
Description
Plug the PC cable into the system interface.
Start SIMOCODE ES.
Open a project.
Select Online → Extended online connection.
Select the type of the PG/PC interface (SIRIUS PtP or PN/IE).
Select the PG/PC interface.
Click the "Start search" button. A search is made for compatible stations.
Select a station.
Load the parameters to the device via "Online → Load to device".