Siemens SIMOCODE pro C System Manual page 324

Industrial controls. motor management and control devices
Table of Contents

Advertisement

Safety and commissioning information for Ex areas
14.2 Dry-running protection for centrifugal pumps by active power monitoring
System test with operating medium
A system test with operating medium is an integral part of any commissioning procedure
(e.g. after changes to parameter settings) and of the "General system test". It might also be
required at shorter intervals if demanded by statutory regulations.
Note
Automation
If you wish to reduce the amount of manual intervention, you can store appropriate
sequences in your process control system for (partially) automated running of the system
test with operating medium.
● Checking a potential drift:
– Set the same operating conditions (medium, flow rate, temperature, pressures, etc.)
– Measure the active power (at least two measured values, e.g. P
– Compare the measured values with those from the previous test.
– Eliminate any causes of deviation.
● Checking the effectiveness of shutdown:
– If not yet done: First enter the relevant values for plant configuration for the trip level of
– If necessary, carry out a teach-in to determine the trip level (see Chapter "Dry-running
– Set the start-up bridging time t
– Start the centrifugal pump filled with operating medium; the pressure-side shut-off
– Set a sufficiently large value for the start-up bridging time t
– Start the centrifugal pump filled with operating medium.
– Begin by setting a sufficiently high flow rate for ongoing operation.
– Reduce the pump's flow rate incrementally until the active power value detected by
324
as for the previous test.
the active power monitoring P
protection for centrifugal pumps" in the manual Parameterizing SIMOCODE pro
(https://support.industry.siemens.com/cs/ww/en/view/109743958)).
valve must be closed. The "dry-running protection" function must shut down the pump
immediately.
the procedure used when starting up the centrifugal pump.
SIMOCODE pro falls below the trip level. The time span during which the flow-rate
remains at a certain value for the active power at each step must be longer than the
delay time t
that has been set. After undershooting the trip level P
V,TRIP
must shut down once the delay time t
(shutdown and delay time) must correspond to the preset parameter values.
and for the delay time for ongoing operation t
TRIP
to 0 s.
BRIDGE
has expired. The system's response
V,TRIP
System Manual, 05/2019, A5E40507475002A/RS-AD/004
and P
).
OPT
MIN
V,TRIP
– coordinated with
BRIDGE
, the pump
TRIP
SIMOCODE pro
.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents