Troubleshooting; Error Buffer - Siemens SIMOCODE pro C System Manual

Industrial controls. motor management and control devices
Table of Contents

Advertisement

Commissioning, service, troubleshooting

13.4 Troubleshooting

13.4
Troubleshooting
13.4.1

Error buffer

SIMOCODE pro has an error buffer in which the 21 most recent errors / faults and "Power -
On" events are recorded with a time stamp. Time stamps are based upon the operating
hours of the device (resolution 1 s), i.e. the length of time for which the device is supplied
with control supply voltage.
The "Error/Fault" and "Power - On" events are logged. Each of these events is given a time
stamp.
● Error/Fault: The last 21 errors are stored in a ring buffer; the incoming error (rising edge)
is always logged. An outgoing error (falling edge) will not be logged.
● Power on: If the most recent entry is "Power - On," this is not logged multiple times.
Instead, the error number is used as a power-on counter. Thus, the error buffer cannot be
deleted by frequent on/off operations.
Entry 1 is the most recent entry and entry 21 the oldest.
This data is displayed via the "SIMOCODE ES (TIA Portal)".
288
System Manual, 05/2019, A5E40507475002A/RS-AD/004
SIMOCODE pro

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents