Siemens SIMOCODE pro C System Manual page 341

Industrial controls. motor management and control devices
Table of Contents

Advertisement

15.4 Technical data of the current measuring modules and the current / voltage measuring modules
Technical data of the current measuring modules and the 2nd generation current / voltage measuring modules
Temperature drift of current
measurement
of the cos phi measurement
(cos phi ≥ 0.5)
of the apparent power
measurement (cos phi ≥ 0.5)
of the active power
measurement (cos phi ≥ 0.5)
of the energy measurement
(cos phi ≥ 0.5)
of the frequency measurement
(cos phi ≥ 0.5)
of the ground-fault detection acc.
to IEC 60947-1, Annex T
in the range 30% - 120% I
in the range 15% - 30% I
Accuracy at 25°C, 50/60 Hz for extended current ranges 2 x I
Temperature drift of current measurement
3UF7110-1AA01-0
3UF7111-1AA01-0, 3UF7112-1AA01-0, 3UF7113-1AA01-0, 3UF7113-
1BA01-0, 3UF7114-1BA01-0
Current measuring accuracy
Accuracy of the cos phi measurement (cos phi ≥ 0.5)
Accuracy of the apparent power measurement (cos phi ≥ 0.5)
Accuracy of the active power measurement (cos phi ≥ 0.5)
Accuracy of the energy measurement (cos phi ≥ 0.5)
Note on voltage measurement
Caution
Note that the supply cables for voltage measurement may require additional cable protection.
Feed-through opening
Current setting 0.3 A - 4 A;
3 A - 40 A
Current setting 10 A - 115 A:
Current setting 20 A to 200 A:
Bus connection
Current setting I
s
Connection screw
Tightening torque
Solid with cable lug
Stranded with cable lug
AWG cable
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
3UF7110-1AA01-0: 0.02% / K
3UF7111-1AA01-0: 0.01% / K
3UF7112-1AA01-0: 0.01% / K
± 1.5%
8)
± 3%
± 5%
± 5%
± 1.5%
± 10% (Class CI-A)
e
± 25% (Class CI-B)
e
Diameter
7.5 mm
14.0 mm
25.0 mm
20 A to 200 A
M8x25
10 Nm to 14 Nm
16 mm
- 95 mm
2
2) 3)
25 mm
- 120 mm
2
4 kcmil - 250 kcmil
< Ie < 8x I
o
o
2) 3)
3UF7113-1AA01-0: 0.01% / K
3UF7113-1BA01-0: 0.01% / K
3UF7114-1BA01-0: 0.01% / K
0.02% / K
0.01% / K
± 3% (typically)
± 5% (typically)
± 5% (typically)
± 10% (typically)
± 10% (typically)
Design of cable insulation
6 kV according to IEC 60947-1
6 kV according to IEC 60947-1
6 kV according to IEC 60947-1
63 A to 630 A
M10x30
14 Nm to 24 Nm
50 mm
- 240 mm
2
2) 4)
70 mm
- 240 mm
2
2) 4)
1/0 kcmil to 500 kcmil
Technical data
341

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents