Mounting, wiring, connecting, system interfaces, configuration guidelines
12.2 Wiring, connecting
Wiring sequence of the removable terminal of the SIMOCODE pro C/V basic units
Proceed as follows:
Table 12- 9
Wiring of the removable terminals of the SIMOCODE pro C/V basic units
Step
Description
1
Connect the cables to the upper and lower terminals.
2
If you wish to use the A/B terminals for PROFIBUS DP, connect the PROFIBUS DP cable shield to the
SPE / PE terminal.
3
Connect the equipment shield to the SPE
1)
Note
Connect SIMOCODE pro via terminal SPE with the maximum possible cross-section and
with as short a cable as possible to the functional ground of the control cabinet, e.g. to the
grounded mounting plate of the control cabinet.
Note
The A / B terminals are an alternative to the 9-way SUB-D connection! Baud rates of up to
1.5 Mbit / s
Note
1) Baud rates > 1.5 Mbit / s
At baud rates > 1.5 Mbit / s, the "Bus" fault is generated and the "Bus" LED lights up.
204
terminal.
1)
are possible.
1)
System Manual, 05/2019, A5E40507475002A/RS-AD/004