Diagram Of Diagnostics Data - Siemens SIMOCODE pro C System Manual

Industrial controls. motor management and control devices
Table of Contents

Advertisement

11.3

Diagram of diagnostics data

The following table shows the diagnostics data in the 3UF50 compatibility mode:
Table 11- 3
Diagram of the diagnostics data in the 3UF50 compatibility mode
Byte.
Setup 3UF50 -
Bit
Device-specific diagnostics
according to DP standard
SIMOCODE DP
6
0x0E
7.0
Free
7.1
Event: DP block
7.2
Event: Emergency start
7.3
Event: HW test OK
7.4
Free
7.5
Event: Ext. event 1
7.6
Event: Ext. event 2
7.7
Event: Ext. event 3
8.0
Warning: Ext. warning
8.1
Warning: Unbalance > 40 %
8.2
Event: Failure PLC-CPU
8.3
Warning: Sensor short circuit
8.4
Event: Cooling down period active
8.5
Status: TPF
8.6
Free
8.7
Free
9.0
Warning: Ground fault
9.1
Warning: Overload
9.2
Warning: Overload + unbalance
9.3
Warning: I1 response level
overshot
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Byte.
Setup 3UF50 -
Bit
Device-specific diagnostics
according to DPV1 SIMOCODE DP
6
0x0B
7
0x81
8
0x04
9
0x00
10.0
Free
10.1
Event: DP block
10.2
Event: Emergency start
10.3
Event: HW test OK
10.4
Free
10.5
Event: Ext. event 1
10.6
Event: Ext. event 2
10.7
Event: Ext. event 3
11.0
Warning: Ext. warning
11.1
Warning: Unbalance > 40 %
11.2
Event: Failure PLC-CPU
11.3
Warning: Sensor short circuit
11.4
Event: Cooling down period active
11.5
Status: TPF
11.6
Free
11.7
Free
12.0
Warning: Ground fault
12.1
Warning: Overload
12.2
Warning: Overload + unbalance
12.3
Warning: I1 response level overshot Warning - Warning level I >
3UF50 compatibility mode
11.3 Diagram of diagnostics data
Equivalent in SIMOCODE pro V
Same as 3UF-50 diagnostics
Event - Startup parameter block
active
Status - Emergency start
executed
No fault - HW fault basic unit
No fault - Module fault
No fault - temporary
components
Event - Ext. fault 5
Event - Ext. fault 6
Warning: Ext. fault 3
Warning - Unbalance
Status - PLC / PCS (intervened)
Warning - Thermistor short
circuit
Status - Cooling down period
active
Status - Test position (TPF)
Warning internal ground fault
or
Warning external ground
fault
Warning - Overload
Warning - Overload + unbalance
181

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents