Commissioning, service, troubleshooting
13.4 Troubleshooting
Event
Description
(alphabetical)
DM-FL
The DM-F Local is in
configuration
"configuration mode"; the
mode
"DEVICE" LED on the front of the
DM-F Local is illuminated yellow.
DM-FL cross
Cross circuit in sensor circuit of
circuit
DM-F Local; the "SF" (general
fault) LED on the front of the
DM-F Local is illuminated red.
DM-FL
The DM-F LOCAL is in the
waiting for
"Waiting for start-up test" status.
start-up test
DM-FP Prm
The parameter settings of the
error
PROFIsafe profile are incorrect
or the set PROFIsafe address is
not identical to the configured
address.
Double 0
Both torque switches have
activated simultaneously. The
motor feeder has been turned off.
Double 1
Both limit switches have
activated simultaneously.
End position
Except positioner 5 control
function: The state of the limit
switches has changed without a
command (positioner has left the
end position without a
command).
External
External ground-fault monitoring
ground fault
has responded. An impermissibly
high residual current is flowing.
External
A signal is pending at the input
fault 1, 2, 3,
(socket) of the "External fault 1,
4, 5 or 6
2, 3, 4, 5 or 6" standard function.
Required
At least one parameterized
function is
function is not supported by the
not supported
version of the basic unit.
Hardware
The SIMOCODE pro basic unit
fault
hardware is defective.
Initialization
The initialization module is
module write-
completely write-protected.
protected
294
Troubleshooting
Complete the
configuration (see manual
"Fail-safe Digital Modules
SIMOCODE pro Safety",
Chapter 7.4)
.
3)
Check the wiring of
both sensor circuits for
cross circuiting
Rectify the fault.
Perform the startup test by
actuating the sensor in the
sensor circuit.
Check the
communication /
PROFIsafe parameters of
SIMOCODE pro that were
set on the IO controller.
Open circuit torque
switch.
Torque switch is
defective.
Limit switch defective
Please check the motor
connection cable for
damage.
Check the motor feeder.
Activate only the functions
that are supported by the
version of the basic unit.
Replace the basic unit.
See Chapter Replacing
SIMOCODE pro
components (Page 279).
Deactivate write protection
of the initialization module
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Acknowledgment /
Contactor
fault rectification
control
Reset
Tripped
Tripped
Tripped
Counter command
Tripped
"OPEN /
CLOSED!"
Reset
Tripped
Tripped
Clear the fault.
Tripped
Error
No.
1)
68
13
14
15
29
56,
57,
58,
59,
60,
61
0
SIMOCODE pro

Hide quick links: