Commissioning With Profinet; Profinet Commissioning Steps - Siemens SIMOCODE pro C System Manual

Industrial controls. motor management and control devices
Table of Contents

Advertisement

Commissioning, service, troubleshooting
13.2 Commissioning
13.2.2

Commissioning with PROFINET

13.2.2.1

PROFINET commissioning steps

Please observe the information in Chapter General information about commissioning and
service (Page 255).
To commission SIMOCODE pro, proceed as follows:
Table 13- 6
Commissioning the basic unit
Step
Description
1
Switch on the power supply. In a fault-free state, the following LEDS should light up green:
"Device" (lights up)
"PORT 1 / PORT 2" when the PROFINET cable is connected (lighted or flashing).
Continue with step 2.
Otherwise, carry out diagnostics according to the LED display. For more information, see Chapter
Diagnostics via LED display on the basic unit and on the operator panel (PROFINET) (Page 264). Try to
rectify the fault.
2
If you want to make SIMOCODE pro available to PROFINET, you must set the IP parameters and the
PROFINET device names. For more information, see Chapter Setting IP parameters and PROFINET
device name (Page 261).
3
Parameterize SIMOCODE pro or check the existing parameterization, e.g. with a PC on which
SIMOCODE ES (TIA Portal) software is installed. For this, connect the PC / PG to the system interface
with the PC cable (see the figure below).
4
Start SIMOCODE ES.
Figure 13-2
260
Connecting a PC to the basic unit
System Manual, 05/2019, A5E40507475002A/RS-AD/004
SIMOCODE pro

Hide quick links:

Advertisement

Table of Contents
loading