Output signals can be increased or decreased by the internal analog output coefficients F1502 and F1506. If the output signal from the
AOUT1 or AOUT2 terminal is not of an adequate level, the signal level can be adjusted by setting the internal analog output
coefficient.
F1502: Coefficient for F1501 (Internal Analog Output Function 1)
F1505: Coefficient for F1504 (Internal Analog Output Function 2)
Note 2: If the coefficients of F1502 and F1505 are smaller than 1, the output signals are decreased.
Bias voltage can be set for each output signal using F1503 or F1506 (internal analog output bias).
Although the negative bias voltage setting is possible, the output signal voltage will be 0V where the output signal voltage is negative.
Note 3: The PID controlled variables are output in the form of absolute value. In case of negative value, the output will be
positive.
F1507
Approach frequency
This function specifies the frequency at which a frequency arrival signal is output.
Code No.
Function Name
F1507
Approach frequency
If the value of any one of F1509 – F1511 is 7 (frequency arrival), the signal is output from control circuit output terminals DO1 to DO3
when the output frequency exceeds the value of F1507."
Similarly, If the value of F1513 is 7 (frequency arrival), the signal is output from control circuit relay output terminals FA1, FB1 or
FC1 when the output frequency exceeds the value of F1507."
Frequency approach signal
F1508
Frequency matching range
This function specifies the out frequency band corresponding to the frequency matching signal.
Code No.
Function Name
F1508
Frequency matching range
If the value of any one of F1509 – F1511 is 5, 6, 14 or 15, the signal is output from control circuit terminals DO1 to DO3 when the
output frequency falls within the value range between ±F1508."
Similarly, for F1513, the signal is output from control circuit relay output terminals FA1, FB1 or FC1.
A MODEL
S06-4A005-B**
20A/10V
S06-4A006-B**
S06-4A009-B**
20A/10V
S06-4A014-B**
50A/10V
S06-4A019-B**
S06-4A025-B**
50A/10V
S06-4A032-B**
100A/10V
S06-4A038-B**
S06-4A049-B**
100A/10V
S06-4A061-B**
S06-4A076-B**
250A/10V
S06-4A092-B**
S06-4A115-B**
250A/10V
S06-4A152-B**
500A/10V
Data Content
0~400Hz
Output
frequency
Data Content
0~10Hz
- 95 -
B MODEL
20A/10V
50A/10V
50A/10V
100A/10V
100A/10V
250A/10V
250A/10V
500A/10V
500A/10V
Setting Resolution
0.01Hz
F1507:Approach frequency setting value
Time
Setting Resolution
0.01Hz
Factory Presets
10
Factory Presets
0