function)
(6) Register address
The register address can be selected through function code [F4103: Modbus register address switchover]. There are two kinds of
addresses.
Refer to the table below for register address.
■Reading register address (F4103=1: register number A)
Processing
method
DEC
2000
2001
2002
2003
2004
2005
2006
2007
Reading
2008~2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020~2029
※1 Please refer to list of alarm codes for communication with dedicated protocol.
※2 STATUSFLAG (status flag)
In RAM bit status, the status flags are shown as follows.
And, the "only vector mode" bit is reset and cleared only in vector mode; all the bits will be cleared in V/f mode. (Clear = 0,
Reset = 1)
Register No.
HEX
7D0H
7D1H
7D2H
7D3H
7D4H
7D5H
7D6H
7D7H
BIT9 and above
7D8H~7D9H
BIT17 and above
7DAH
7DBH
7DCH
BIT8 and above
7DDH
BIT5 and above
7DEH
7DFH
7EOH
7E1H
7E2H
7E3H
7E4H~7EDH
Description
Alarm content
0=No alarm; other=list of alarm codes ※1
Reading of command frequency
Reading of output frequency
Reading of output current
Reading of DC voltage
Reading of radiator temperature
Reading of load factor
Reading of Operation Status 1
JOG+16
0000: speed segment 0, JOG operation
BIT0~BIT4
Operation by external analog input frequency
BIT5
Operation by option input frequency
BIT6
BIT7
BIT8
Reading of Operation Status 2
STATUS FLAG(32bit) ※2
Reading of Operation Status 3
Reading of Operation Status 4
Reading of external terminal input status 1
BIT0~BIT7
Reading of external terminal output status 1
BIT0~BIT2
BIT3~BIT4
Reading of output voltage
Reading of VRF/IRF control terminal input value
Reading of VIF1 control terminal input value
Reading of AOUT1 output value
Reading of AOUT2 output value
System reversed
- 186 -
th
speed operation (operation status)
st
00001: 1
speed operation
nd
00010:2
speed operation
.........................
th
10000: 16
speed operation
(operation status)
(operation status)
1=warning; 0=no warning
1=alarm; 0=no alarm
System reversed
System reversed
System reversed
System reversed
DI1~DI8 (ON/OFF)
1=ON; 0=OFF
System reversed
DO1~DO3 (HIGH/LOW)
1=LOW; 0=HIGH
RY1~RY2 (HIGH/LOW)
1=HIGH; 0=LOW
System reversed
Reversed