following main control board.
JP2 is a switch for turning ON / OFF the terminating resistor. Please set only the farthest terminating resistor switch of
the inverter to ON. (Factory preset= OFF: terminating resistor OPEN).
⑥ Contact output terminals
1) Signal mode switching for emergency stop (multifunctional input ES terminal)
The figure below shows an example of signal switching when the multifunctional input terminal is set for the external
emergency stop (ES) command.
A signal action is selected using the function code F1413: ES input terminal function.
When "normally open"
signal is input:
⑦ Jumper (JP2 communication terminal resistor ON selector jumper)
When several inverters are communicating, place the JP2 of the farthest inverter into ON position, the terminal resistor
now will be connected, while its factory setting is OFF.
When "normally
closed" signal is
input:
Terminal resistor selector switch
- 21 -