Note 1: For torque limiter (power running) values corresponding to control circuit terminal input signal, the change
range of mode A is 0-200%, the change range of mode B is 0-150%.
Note 2: This function is effective only when selected by the speed control of vector control (F1001=2 or 3).
Reference parameter
F1001 (motor control mode selection)
F6001 (torque limiter (power running))
Torque limiter analog input function (regeneration)
F6004
The function to change the torque limiter values in braking status with the analog input command of control circuit terminals VIF1,
VIF2 and VIF3.
Code No.
Function Name
F6004
Torque limiter analog input function
(regeneration)
● When F6004=0, the torque limiter during braking will use the value set by F6003.
● When F6004=1, 3, 5, the torque limiter values in braking status are set by input values of control circuit terminals VIF1, VIF2
and VIF3 (0-5V).
● When F6004=2, 4, 6, the torque limiter values in braking status are set by input values of control circuit terminals VIF1, VIF2
and VIF3 (0-10V) or potentiometer.
● When F6004=7, 8, 9, the torque limiter values in braking status are set by input values of control circuit terminals VIF1, VIF2
and VIF3 (4-20mA).
Torque limiter (brake)
Note 1: For torque limiter (brake) values corresponding to control circuit terminal input signal, the change range is
0-100%.
Note 2: This function is effective only when selected by the speed control of vector control (F1001=2 or 3).
Reference parameter
F1001 (motor control mode selection)
F6003 (torque limiter (brake))
Multiple for starting excitation current
F6005
The function to set the starting excitation current in vector control mode (speed sensored and speed sensorless).
Correspond to DC braking force in V/f mode during startup (F1114).
Code No.
Function Name
F6005
Multiple for starting excitation current
● The factory presetting values are set to be equal to (1.0 multiple) the excitation current of corresponding motor.
● When setting this function, please input the ratio value related to the motor excitation current. (Maximum of 2 multiples)
Note 1: If excitation current is over-increased, there may be a shutdown because of over-current.
Note 2: When the braking force is not changed and the excitation current ratio is enlarged, the current limiting function
will be enabled because of the over-current caused by some reason.
0:F6003
1:External analog VRF1voltage(0~5V)
2 : External analog VRF1voltage ( 0 ~ 10Vor
potentiometer)
3:External analog VRF/IRFvoltage(0~5V)
4 : External analog VRF/IRFvoltage ( 0 ~ 10Vor
potentiometer)
5:Reserved
6:Reserved
7:Reserved
8:External analog VRF/IRFcurrent(4~20mA)
9:Reserved
Input value of control circuit terminals
for applicable motor
0.1~2(
- 149 -
Data Content
Data Content
Factory
Setting Resolution
Presets
1
0
Factory
Setting Resolution
Presets
0.01
1