Sanken S06-4A005-B Instruction Manual page 185

High performance vector control multifunction inverter
Table of Contents

Advertisement

SUM
3) Message from inverter to computer (RTU) (abnormal response)
Item
IN
Inverter number
OP
Command code
DT
SUM
OP category
In OP in RTU format, 03H: register reading and 10H: register writing are existed. The followings are descriptions for registers
used in batch operation.
1) Register reading
·
OP=03H
·
During register reading, the data listed in the following table can be read.
Refer to the [(6) Register address] described later for the register address of all data.
Up to 5 data can be read simultaneously.
For setting errors of function codes, please refer to list of error codes.
2) Register writing
·
OP = 06H (single register writing)/OP = 10H (continuous register writing)
·
With register writing, the data can be written and changed.
Refer to the [(6) Register address] described later for the register address of all data.
Even with the continuous register writing, only one data can be writen into the function code data at each time.
⑴→'02'(2)→'F3'
2) Number of register (2 byte fixed)
Example: number of registers: 2
(3)→'00'(4)→'02'
3) Number of data (1 byte fixed)
Example: 4 data are read
(5) →'04'
4) Data content (variable, byte = number of data (1))
Example: 4 data are read
(6)→'00' (7)→'00' (8)→'13' (9)→'88'
(1)
Example ②: Data content written into one register (06H)
1) Setting of register (2 byte fixed)
Example: register set as 03E8H
(1)→'03' (2)→'E8'
2) Setting of data content (2byte fixed)
Example: data value set as 0001H
(3)→'00' (4)→'01'
・Data (DT) (4byte)
(1)
Example ③ Data content written into the register (10H)
1)Register number (2 byte fixed)
Example: register number 03E8H
⑴→'03'⑵→'E8'
2)Setting of number of registers (2 byte fixed)
Example: writing in two registers
⑶→'00'⑷→'02'
·Data (DT)(4byte)
(1)
Checksum
CRC check (2-byte fixed)
Name
0: Broadcast mode
1-254: inverter number of receiver
Data format is fixed as 1byte
Inverter number is the data set by function code F4006
Example: inverter number 2 ②→'02'。
Computer-sent command code +80H;
Top digit 1 means abnormality.
Data
Abnormality response data format is fixed as 1-byte
For alarm contents, see list of alarms for dedicated protocol.
Checksum
CRC check (2byte fixed)
(2)
(3)
(4)
(5)
(2)
(3)
(4)
(2)
(3)
(4)
Description
- 184 -
(6)
(7)
(8)
(9)