Reference parameter
F1701 (output current limiting)
st
th
F1012~F1015 (1
~ 4
acceleration time)
st
th
F1016~F1021 (1
~ 4
deceleration time)
Current limit
(F1701)
Output frequency
F1704
Overload alarm level setting value
The function to output a overload pre-alarm signal for the current from the control signal output terminal (set by F1509~F1511) or
multi-function relay (set by F1513) when the inverter is powered off because of overload or there is an abnormal situation at the side of
the loading device.
Code No.
Function Name
F1704
Overload alarm level setting
value
● The setting values are set according to the ratio with the rated current.
● When the output current from the inverter exceeds the values set in F1704, the overload pre-alarm signal will be output.
Reference parameter
F1509~F1511 (select output terminal D01 ~ D03)
F1513 (select contact output of relay 1)
Motor type
F1705
The function to select the type of the motor connected to the inverter.
Code No.
Function Name
F1705
Motor type
● Change the actions of the electric thermistor according to the motor types. Refer to F1702 (Electric thermistor setting)
Reference parameter
F1702 (Electric thermistor setting)
F1706
Function to switch between "OV" and "LV" alarms when stopped
Select the alarms of "OV" (overvoltage) and "LV" (lowvoltage) when the inverter is stopped.
Code No.
Function Name
F1706
Function to switch between
"OV" and "LV" alarms when
stopped
● In the seven-segment monitor on the operation panel, overvoltage is shown as
Note 1: With this function, even when the alarm is disabled, the protecting action is still effective. But the alarm will not be
displayed on the operation panel, the alarm relay will neither output, therefore the reason of the alarm can not be
detected.
Note 2: When the display of
Acceleration &
With output current
deceleration slopes
limiting at constant
selected by F1703
speed(F1703≠0)
Data Content
A MODEL
B MODEL
Data Content
General-purpose motor
1:
2:
Exclusive motor for the inverter
Data Content
"OV" enabled, "LV" disabled when stopped
0:
"OV" disabled, "LV" enabled when stopped
1:
"OV" disabled, "LV" disabled when stopped
2:
"OV" enabled, "LV" enabled when stopped
3:
&
as well as the relay output influence other logic actions, please set this function.
- 106 -
output current
Time →
Setting Resolution
20~200%
20~150%
Setting Resolution
Setting Resolution
, lowvoltage is shown as
Factory Presets
1%
150
120
Factory Presets
1
1
Factory Presets
1
0
.