F5003
Motor frequency rating
F5004
Motor speed rating
F5005
Motor insulation type
F5006
The motor's rated voltage during auto
tuning of motor parameters
F5007
Rated motor slip
※ If motor parameters are known, please enter the parameters into the following function codes.
F5009 Motor's primary resistance (Ω or mΩ)
F5010 Motor's secondary resistance (Ω or mΩ)
F5011 Motor's primary inductance (mH)
F5012 Motor's secondary inductance (mH)
F5013 Motor's mutual inductance (mH)
F5014 Motor's excitation current (A)
F5015 Motor inertia (kgm
F5016 Load inertia ratio
[Motor parameter auto tuning steps]
(1)
Setting of motor ratings
Set all the motor ratings into function codes F5001 — F5005 correctly.
Press [PROG] key to display function codes
Select F5001 using numeric key
Press [ENTER] key to input numerical values
After input, press the [ENTER] key again to confirm
Set function codes F5002 — F5005 in order in the same way.
① F5001 Motor poles, voltage, and capacity
The configurable values and contents denoted are as follows.
1) Number of poles: 2 — 8 (4 types).
2
2) Rated voltage: the setting range of rated voltage is denoted by serial numbers. Unit: [V].
No.
Corresponding rated voltage
3) Motor capacity: the setting range of motor capacity is denoted as follows. Unit: [kW].
0.37
3.0
18.5
The symbol
indicates a space.
Example) When using a motor of 4 poles, 220V, 2.2KW, the 7-segment monitor displays the following:
44 2.2
Operation example) in case where a motor of 4 poles, 200V, 2.2KW is used, operation for changing the rated voltage is
as follows:
44 2.2 → 4
Note: During vector control and auto torque boost control, standard values of various control constants necessary for
inverter control need to be obtained from the settings of the function code, thus please make correct setting
according to the motor used.
2
)
4
6
8
1
2
200
220
0.55
0.4
3.7
4.0
22.0
30.0
4 2.2 → 4
5 2.2
4
5
10~400Hz
0~24000rpm (1rpm stepping)
1: Type A
2: Type E
3: Type B
4: Type F
5: Type H
0: Use function code F5001
selected voltage
100~460 (voltage of F5001 is invalid)
0~50%
3
4
5
230
380
400
0.75
1.1
5.5
7.5
37.0
45.0
- 36 -
6
7
8
415
440
460
1.5
2.2
11.0
15.0
55.0
75.0