Item
IN
Inverter number
OP
Command code
DT
Data
SUM
Checksum
2) →Message from inverter to computer (RTU) (normal response)
Item
IN
Inverter number
OP
Command code
DT
Name
0: broadcast mode
1-254: inverter number of receiver
Data format is fixed as 1byte
Inverter number, the data set by function code F4006
Example: inverter number 2 ①→'02'
Command code (1byte fixed) (03H, 06H, 10H)
Example ①: Data content read from register (03H)
1) Register number (2-byte fixed)
Example: register number 07D0H
⑴→'07',⑵→'D0'
2) Number of registers (2-byte fixed)
Example: two registers
⑶→'00',⑷→'02'
·Data (DT)(4byte)
(1)
Example ②: Data content written into one register (06H)
1) Setting of registers (2-byte fixed)
Example: register set as 03E8H
(1)→'03' (2)→'E8'
2) Setting of data content (2-byte fixed)
Example: data value set as 0001H
(3)→'00' (4)→'01'
・Data (DT) (4byte)
(1)
Example ③ Data content written into the register (10H)
1) Register number (2-byte fixed)
Example: register number 03E8H
⑴→'03'⑵→'E8'
2)Setting of number of registers (2-byte fixed)
Example: setting register
⑶→'00'⑷→'01'
3)Number of data (1-byte fixed)
Example: setting data
⑸→'02'
4)Data content (variable, byte = number of data (5))
Example: setting register 0001H
⑹→'00'⑺→'01'
·Data (DT)(7byte)
(1)
CRC check (2 byte fixed)
Name
0: Broadcast mode
1-254: inverter number of sender
Data format is fixed as 1byte
Inverter number, the data set by function code F4006
Example: inverter number 2 ①→'02'
Same as the code sent from computer to inverter
Data
Example ①: Data content read from register(03H)
1) Setting of register (2 byte fixed)
Example: register set as 03F3
Description
(2)
(3)
(4)
(2)
(3)
(4)
(2)
(3)
(4)
(5)
(6)
Description
- 183 -
(7)