Sanken S06-4A005-B Instruction Manual page 82

High performance vector control multifunction inverter
Table of Contents

Advertisement

Start delay time
F1105
This function is used to set the time until the inverter starts operation after inputting an operation signal.
Code No.
Function Name
F1105
Start delay time
● This function is useful for setting the delay time with a sequence circuit for changeover between inverter/mains power, etc.
● When a switch between the motor and the inverter turns on at the same time as input of the operation signal, set F1105 to
approximately 0.5 sec.
Start standby time
F1106
Start standby frequency
F1107
Through the use of output frequency standby function, this function is used to keep the big inertia load in temporary standby by
increasing the frequency when starting and to increase frequency when the speed goes up, so as to facilitate a smooth acceleration.
Code No.
Function Name
F1106
Start standby time
F1107
Start standby frequency
● In the F1106, if a value other than 0 is set, when the frequency set by F1107 is reached by acceleration, the frequency increase
can be locked only by using the time set by F1106 (output frequency standby)
Note 1: This function is inactive when the acceleration/deceleration curve is S-shaped curve (F1010 = 2).
Note 2: If the starting frequency setting is higher than standby frequency, use the starting frequency to realize standby.
Note 3: If target frequency is lower than the standby frequency, standby action will not be executed.
Note 4: Standby action will not be executed during deceleration.
Target frequency
Standby frequency
Starting frequency
F1103
F1108
Restart after momentary power failure
Whether the inverter resumes operation after it stops due to a momentary power failure can be specified using this function. This
function works properly only after a momentary power failure. If the duration of the power failure is longer, correct action can not be
made as the control power supply is lost, as shown in the following table.
Code No.
Function Name
F1108
Restart after momentary power
failure
0~5s
O
Delay time
0.0~120.0s
0.05~60.0Hz
During acceleration
F1107
Standby time
F1106
Do not restart
0:
1:
Restart
Compensation for momentary
2:
power failure
Data Content
Operation signal
Time
Data Content
During deceleration
During acceleration
Time
Data Content
Setting Resolution
- 81 -
Setting Resolution
0.1
Setting Resolution
0.1s
0.01Hz
Standby time
F1106
Factory Presets
1
Factory Presets
0
Factory Presets
0
5
0