F1502
Internal analog output coefficient
F1505
Internal analog output
coefficient 2
F1503
Internal analog output bias 1
F1506
Internal analog output bias 2
The methods of conversion between output values of possible output analog signal from AOUT1 or AOUT2 terminal and actual values
are shown in the table below.
F1501
F1504
Output signal content
Set value
0
No function
1
Set frequency (Hz)
2
Output frequency [Hz]
3
PID1 feedback value [Hz]
4
PID2 feedback value [Hz]
5
Output current (A)
6
Output voltage [V]
7
DC voltage [V]
8
Radiator temperature [℃]
9
Load factor [%] (integral value of the electric
thermistor)
10
Load factor [%] (ratio to rated current)
11
VRF1analog input value [V]
12
VRF/IRFanalog input value [V]
13
Reserved
14
Speed [rpm]
15
Active power [kW]
16
Apparent power [kVA]
17
PID1 command value [Hz]
18
PID1 input deviation value [Hz]
19
PID2 command value [Hz]
20
PID2 input deviation value [Hz]
24
External PID1 output value [Hz]
25
External PID2 output value [Hz]
35
Command frequency [Hz]
36
Command torque [%]
*1 The positive and negative values of command torque are output with 5V as the center.(0V=-200%, 5V=0%, and
10V=200%)
Note 1: Maximum allowable current: 15mA.
(But, the converted value is no-load output voltage. If the output current increases, the output voltage will decrease.
In this case, the signal output can be adjusted using output coefficient.)
*1)Inverter capacity and output current conversion methods
4:PID2 feedback value [Hz]
5:Output current (A)
6:Output voltage [V]
7:DC voltage [V]
8:Radiator temperature [℃]
9:Load factor [%] (electric thermistor integrated
value)
Load factor [%] (ratio to rated current)
10:
11:VRF1analog input value [V]
12:VRF/IRFanalog input value [V]
13:Reserved
14:Speed [rpm]
15:Active power [kW]
16:Apparent power [kVA]
17:PID1 command value [Hz]
18:PID1 input deviation value [Hz]
19:PID2 command value [Hz]
20:PID2 input deviation value [Hz]
21~23:For factory adjustment
24:External PID1 output value [Hz]
25:External PID2 output value [Hz]
26:For factory adjustment
35:Command frequency [Hz]
36:Command torque [%]
39:Reserved
99:For factory adjustment
1
Model
0~20
0~±10V
Conversion method
120Hz/10V
120Hz/10V
120Hz/10V
120Hz/10V
*1
500V/10V
500V/5V
100℃/8V
100%/5V
100%/5V
4-20mA current input,20mA/10V
0-5V voltage input,5V/5V
0-10V voltage input,10V/10V
1800rpm/5V
10kW/10V
10kVA/10V
120Hz/10V
120Hz/10V
120Hz/10V
120Hz/10V
120Hz/10V
120Hz/10V
120Hz/10V
400%/10V(※1)
Output current signal conversion
method
- 94 -
0.01
1
0.1V
0