Note: In case of braking through an external circuit, please set F1115 = 99.
*1
Since the protection actions will not be executed when F1115 = 98, the discharge resistor and the device may be damaged.
Please note this when setting.
*2
The representative parameters that are suitable for various models have been input.
When setting F1115 = 2-25, if it is judged that excessive current will flow in the brake resistor for a long time, in order to prevent the
brake resistor connected from burning damage, the actions of braking circuit drive element shall be stopped in a certain period of time.
Discharge resistor on signal output time
F1116
This function is used to output signals from a multifunctional output terminal for the time set with F1116 when the discharge resistor
for regenerated power discharge is turned on.
Code No.
Function Name
F1116
Discharge resistor on
output time
● Set one of F1509-F1511 to"32" for the multifunctional output terminal setting. The discharge resistor on signal is output from the
terminal which is set to"32".
● During regenerated energy discharge, the discharge resistor switches between ON and OFF very quickly and repeatedly. The
Discharge Resistor on Signal function facilitates the measurement of this high-speed on/off operation with a narrow pulse width
in external equipment. The narrow pulse width of the on/off operation is expanded by the time set with F1116 and output by a
multifunctional output terminal.
Example) When the Discharge Resistor on Time F1116=0.1 (s).
Discharge resistor
ON/OFF signal
Multifunctional output =32
ON/OFF signal
Display Function
Monitor display selection
F1201
A function for switching the display contents of operation panel.
Code No.
Function Name
F1201
Monitor display selection
● The change of the display value and display method in stopped state, standby state as well as operating state is shown in the
following table.
F1201
1
Flashing output frequency
2
Flashing 0 [A]
3
Flashing speed (※1)
4
Flashing 0 [%]
5
The output monitor can be changed using F1202.
(※1)The display contents may vary depending the motor control mode. The display contents are as shown in the table below.
Motor control mode
Sensorless vector control
Others
(V/f·vector)
Note: By using F1603, this code can be set even when the operation function is locked.
External brake unit
99:
signal
0.01~10s
1:
Frequency
Output
2:
current(A)
Speed of rotation
3:
Load factor
4:
5:
No unit display
Stopped
In operation (operating)
Estimated speed of motor
Detecting speed of PG sensor
Data Content
Data Content
(Hz)
(rpm)
(%)
Standby/Operating
Normally-on output frequency
Normally-on output current
Normally-on speed (*1)
Normally-on load factor
Stopped
0
Detecting speed of PG sensor
- 84 -
Setting Resolution
Factory Presets
0.01s
0.1
Setting Resolution
Factory Presets
1
1