Operation command values can be changed using the status of multifunctional input terminals. According to the status of
multifunctional input ROPE or RCOM, the operation commands as shown in the table below can be selected. See F1101 in
Chapter 7-3 for details.
6-2-8
Operation confirmation
After setting has been made by following the steps for test run, the operation shall be confirmed as follows.
Once the inverter or motor is in abnormal conditions, please stop operating immediately. See [Chapter 9 Fault Analysis] for
details.
(1) Test run steps
Please refer to the operation methods of operation panel for implementation of 5Hz operation.
Table 6-10 Test run steps
Step
Connect the power supply after check the wiring
Set the operating frequency to 5Hz according to
※ The state where F1101 (operation command selection) is set to 1 (operation by operation panel)
After power input, check that the frequency "
Set the frequency to a low frequency of about 5Hz through the operation panel. (Check that the set frequency
displayed on LED monitor is flashing)
Press [DRIVE] key to start forward running operation.(Check that the set frequency displayed on LED monitor is
flashing)
Press [STOP] key to stop operation of the equipment.
(2) Confirmation items during test run
Please confirm the contents listed in the table below
Table 6-11 Confirmation items during test run
Motor rotation direction
Motor operation 1
Motor operation 2
Inverter fan operation
Inverter display and others
※ When it is confirmed that there is no problem, please increase the set frequency before operation. Similarly, for the
operation with increased frequency, the above confirmation items shall also be checked.
(3) Operation preparation
After confirmation of test run and normal operation confirmation of motor, please implement the connection with the
mechanical system.
① Please set the function codes related to machine action.
② Check the interface matched with peripheral mechanical equipment.
ON
OFF
OFF
ON
ON
ON
ROPE terminal
RCOM terminal
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Operation
the operation panel
Press [DRIVE] key
Press [STOP] key
Item
Is it the specified rotation direction?
Are the acceleration and deceleration smooth?
Is there any abnormal sound or vibration?
Is the fan running?
Are the display on operation panel and equipment normal?
- 39 -
The method selected by F1034
The method selected by F1035
The method selected by F1036
Operation command
The method selected by F1101
Operation panel
Communication
Terminal block (FR terminal, RR terminal)
Display
" displayed on the operation panel is flashing.
Result