Sanken S06-4A005-B Instruction Manual page 164

High performance vector control multifunction inverter
Table of Contents

Advertisement

Recommended Function code value
No.
No.
Function Name
1
F1001
Motor control mode selection
2
F8007
Water supply Optional modes
3
F3201
PID control action selection
4
F1101
Operation command selection
5
F1109
Direction of rotation of motor
6
F1007
Upper frequency limit
7
F1008
Lower frequency limit
8
F1012
1st acceleration time
9
F1016
1st deceleration time
10
F1003
V/f pattern
11
F1004
Torque boost
12
F1102
Starting method
The following is the set of command and feedback
13
F8022
Pressure command
14
F3002
Switch analog input
15
F8023
Offset
feedback
16
F8024
Pressure
feedback
17
F8025
The ratio of pressure upper limit
18
F8026
The ratio of pressure lower limit
19
F8027
The slope of pressure
acceleration and deceleration.
20
F3003
P gain
21
F3004
I gain
22
F3005
D gain
23
F1104
Operation start frequency
24
F3007
Filtering time constant
Please make sure and regulate the following set
25
F1108
Restart after momentary power
failure
*1:If the momentary restart is set for valid, the over current may be occur when reset, please take care of that case.
Note: To avoid the function code being affected from unreasonable setting code, when the single-pump mode needs to apply
at the sleep/auxiliary pump, we strongly recommended the following function code: F1008 ≥ 10Hz;F1104 = 0.01Hz
Recommended
Value
1
15
1
1 or 2
2
45~50 Hz
20~35 Hz
5~30 sec
5~30 sec
2
0 %
1
0.100~2.000MPa
7
pressure
of
analog
0.000~±9.999
gain
of
analog
Set pressure upper
limit according to
actual commend
Set pressure lower
limit according to
actual commend
0.01~0.4
0.1~5.0
0.1~5.0
0
1~10 Hz
10
0 or 1
(Note)
Please make sure the value at the beginning
Single-pump water supply mode
Set automatic restart for 2 at the power off
Fixed at the positive direction
Set it according to the use of pump
Set to without overcurrent and overvoltage
set it according to pump
Set it according to use. F8029 is second pressure
command.
VRF/IRF:4~20mA
Set it according to pressure sensor.
VRF/IRF (at 7): 4~20mA
Be used in the situation of pressure command is
error.
Setting for the rate of change of pressure
command.
Please increase it with set value when the
command is less than 1Mpa.
Keep it for 0
Please increase the set when stop the inverter by
signal of potentiometer and set it more than 0 when
the inverter needs to standby.
About 100ms
Set it for 1 when needs to restart after power
failure. *1
- 163 -