Starting • control function
Operation command selection
F1101
A function for selecting whether the operation/stop command of inverter is sent through operation panel or through external signals.
Code No.
Function Name
F1101
Operation command
selection
● When F1101=2 (external terminal), the input signals of control terminals FR and RR are active. Other control terminal inputs are
always active because they are not related to F1101 data.
● The operation control authorization can be set using external terminals POPE and RCOM. When using external terminals, the
operation control authorization is as shown in the table below.
ROPE
RCOM
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Note 1: When ROPE=OFF and RCOM=OFF, the operation control authorization of F1101 is active. When any one terminal of
ROPE and RCOM is ON, the operation control authorization depends on the terminal status of ROPE and RCOM
regardless of what the set status of F1101 is.
Note 2: Shutdown by『STOP』key on operation panel is always active regardless of the status of ROPE and RCOM terminals.
Starting method
F1102
A function for selecting the starting method.
Code No.
Function Name
F1102
Starting method
● The so-called "flying start" is a method for starting from the frequency corresponding to the motor speed detected so as to reduce
the impact at startup when the motor starts from idling condition. However, in this case, if there is an electromagnetic contactor
between the motor and the inverter, please set the electromagnetic contactor ON in advance, and then input operation signal.
● The so-called "started by starting frequency after DC braking" means the motor is stopped by DC braking before being started in
applications such as reverse run of fan against wind, in which the inverter is stopped while the motor is rotating due to other
factors. This is an effective method to reduce the impact at startup. See F1112- F1114 for DC braking setting.
● Flying start is executed when the alarm is automatically reset and restarted after momentary power failure regardless of the
setting value of F1102.
Data Content
1:Operation panel
External terminal
2:
Communication
3:
Operation Command
The method selected by F1101
Operation panel
Communication
Terminal block (FR terminal or RR terminal)
Data Content
Starting frequency
1:
Flying start
2:
3:
Starting frequency after DC braking
OFF
Operation signal
Frequency
equivalent to
the motor speed
Starting frequency
Setting Resolution
Setting Resolution
ON
F1102=2
F1102=1
t=0
Time
- 79 -
Factory Presets
1
1
Factory Presets
1
1