●See items of F1002 for input modes.
●Even if 1DFA and 1DFB are ON, the frequency setting value in multi-segment speed (2nd - 16th speed) operation or JOG operation
is still the value set by F1021 or F2102 — F2116.
●The same VIF input can be specified by F1002, F1034, F1035, and F1036.
●When any one code of F1034 - F1036 is set to VIF current input, the input resistance of VIF terminal changes as the switching of
1DFA and 1DFB. Please note this when using VIF current input.
F1037
Terminal block step settings
When the 1 speed frequency setting mode of the terminal block stepping function is selected(F1002 = 21), The function is
effective. At this point, the set value of F1037 is the frequency variation of each step/s clock Using this function, please combine with
the instructions of F1002=21 to operate.
About the use of step function and the display frequency instructions of operation panel: at runtime, if the AD2 and AD3 is
ON, the panel displays the setting frequency; when the AD2, AD3 is OFF, the panel will display the current output frequency after 1 s.
When to stop running,, the panel displays the setting frequency.
F1038
Terminal block stepping
reset
When 1 speed frequency is selected to terminal block stepping function (F1002 = 21), this function is effective. At this point, the
F1038 can choose from three ways, and it can only be amended, when the inverter stops instead of operating.
When F1038 = 0, the setting frequency of inverter will remain the same value, even if the inverter stopped or lost its power.
When F1038 = 1, the setting frequency resets after the power is OFF. When the power is ON again, the setting frequency turns 0.
When F1038 = 1 and the power is OFF, the original setting frequency remains unchanged, even if the power is ON again.
When F1038 = 2, the setting frequency will be reset after the frequency converter stops. Whatever the frequency
converter runs normally or alarms downtime, the setting frequency will be reset.
Note: when setting F1038 = 2, because the setting frequency was reset, the function of instantaneous stop and restart (F1108 = 1, 2) is
invalid.。
Frequency held or
- 78 -