7) Cycle completion signal of simple graph operation
If a control terminal output function is set in cycle completion of simple graph operation (any one of F1509~F1511 is 3),
before the operation timer T0 stops the inverter or enters into DC braking and braking excitation, the open-circuit output
of collector between control circuit output terminal and DCM1 & 2 is set to ON and is about 200ms. Please put the
external action command to OFF after one cycle is completed, or use it when peripheral equipments and the programs are
required to be synchronized.
Note 1: There is an output when the cycle completion signal of simple graph operation passes the T0. When an
output is not wanted, make a setting beyond F1509~F1511=3, or set the operation timer T0 to 0.0s.
Note 2: On the last operation timer when the total cycle (simple graph operation repetition count) is completed,
when the inverter stops or starts DC braking and braking excitation, the cycle completion signal which
has no relationship with the timer status will be ON.
Frequency
Output terminal DO1~3
Various relay output
8) Figure of simple graph operation and function code setting
The following figure summarizes the correspondence between the actions of simple graph operation and the function
codes.
Operation timing T0~T15: F2203~F2217=0~65000s
Multi-speed frequency 1~15: F2101~F2115=0~600Hz
Forward/reverse, acceleration/deceleration time: F2221~F2235
Repetition count: F2202=0~250 (0: without limit)
Operation signal
1-Speed
Forward
Reverse
Acceleration/deceleration
Forward/reverse
9) Midway stop and midway start of simple graph operation
During simple graph operation, when the inverter must be stopped because of some undiscovered reason, the deceleration
time during this period can be set independently and separated from the operation timer.
When stop command between operation timers T1~T15 (including alarms) are entered into the inverter, the inverter will stop
deceleration or idle running, and stay at the midway stop status during simple graph operation. The stop deceleration time
When Idle running stops
2-Speed
4-Speed
5-Speed
6-Speed
3-Speed
- 121 -
Deceleration Stop
Inverter stops orunder DC
braking and braking
excitation
About 200ms
about 200ms
When deceleration stops, DC braking stops
and braking excitation stops
7-Speed
8-Speed
11-speed
9-Speed
10-speed
1 cycle
1-speed
14-speed
13-speed
(stop)
12-speed
15-speed
Time