A function for selecting the frequency setting method for the 1st speed frequency operation.
Code No.
Function Name
F1002
1st speed frequency
selection
● Reading analog frequency
A function which takes the result of calculation of the 3 channels of control circuit's analog input terminals VIF1, VIF2, VIF3
(frequency command) carried out internally by the inverter as the inverter's command frequency.
The inverter converts the input command of each channel into a frequency by adjusting the bias and gain code. The results are
added or subtracted according to the value of F1002.
A negative result is always regarded as 0. The upper limit of the calculation result is determined using the upper frequency
limit (F1007, F1316 and F1317).
● F1002 = 21: Terminal block stepping function.
This function allows the target frequency to be increased or decreased under ON/OFF status control of the external control
terminals. This function is useful when it is difficult to input an external analog frequency or to set a frequency from the
operation panel.
1)
Related function codes and multifunctional input terminals
Function code
F1002=21
· If the first speed frequency selection is set to terminal block stepping (F1002= 21), a frequency setting value can be
entered only from external control input terminals AD2 and AD3 of the inverter host.
Note: The frequency cannot be changed from the operation panel.
· It is a function which takes AD2 terminal as the Up terminal of the set frequency and AD3 terminal the Down terminal
of the set frequency.
Note: When F1002=21 is selected, the AD2 and AD3 terminals set using F1414-F1421 can not be used for the 2nd, 3rd,
or 4th acceleration/deceleration command.
2) Increasing or decreasing the set frequency
1:Operation panel
2:External analog VRF1voltage(0~5V)
3:External analog VRF1voltage(0~10Vor potentiometer)
4:External analog VRF/IRFvoltage(0~5V)
5:External analog VRF/IRFvoltage(0~10Vor potentiometer)
6:Reserved
7:Reserved
8:Reserved
9:External analog VRF/IRFcurrent(4~20mA)
10:Reserved
11:External analog VRF1voltage+VRF/IRFvoltage
12:Reserved
13:Reserved
14:External analog VRF1voltage-VRF/IRFvoltage
15:External analog VRF/IRFvoltage-VRF1voltage
16:External analog VRF1voltage
17:Reserved
18:External analog VRF1voltage+ VRF/IRFcurrent
19:External analog VRF1voltage-VRF/IRFcurrent
20:External analog VRF1current-VRF/IRFvoltage
21:Terminal block stepping
22:Communication
25:Pulse train input(Optional function)
26:External analog VRF1forward / reverse run operation(0~
10V、5V reference)
27:External analog VRF/IRFforward / reverse run operation(0~
10V、5V reference)
28:Reserved
29:Reserved
Inverter control terminal
AD2
Up terminal
AD3
Down terminal
COM1
Digital signal common terminal
COM2
Digital signal common terminal
Data Content
- 66 -
Setting
Factory Presets
Resolution
1
1