Overcurrent during
deceleration
Momentary
overload during
acceleration
Momentary
overload during
constant speed
Momentary
overload during
deceleration
Overload during
acceleration
Overload during
constant speed
Overload during
deceleration
Overvoltage during
acceleration
Overvoltage during
constant speed
Overvoltage during
deceleration
Brake resistor
overvoltage
protection
Disconnection of
feedback signal
cable
(during PID control
action)
7-segment
Alarm description
monitor display
Overspeed
Modbus
communication
timeout
Power supply
abnormality
Missing output
phase
Missing input phase
Check grounding
short-circuit current
Disconnection
PG pulse feedback
signal cable
Position
counter abnormality
Cooling fan
abnormality
Main relay
abnormality
Excessive acceleration rate?
Setting for current limiting function
(F1701) too high?
Abrupt change (increase) in load?
Setting for current limiting function
(F1701) too high?
Excessive deceleration rate with a
2
GD
?
Setting for current limiting function
(F1701) too high?
Motor operated with an excessive
load?
Electrothermal level set properly?
2
Load GD
too large?
Did start-up occur during idle run?
Is motor being turned by other
force?
Excessive deceleration?
Braking frequency too high?
Feedback signal cable
disconnected?
Feedback signal correct?
Gain frequency correct?
(F1402, F1404)
Check points
Over-shoot or under-shoot
happened?
Communication cable
disconnected?
+24V power supply output from the
control
circuit
shorted?
Missing an output phase?
Missing an input phase?
Short-circuited when grounding?
of
Feedback signal cables are well
connected?
Is motor being driven by other
deviation
force?
Cooling fan is working?
Turn off the power and wait until
the CHARGE lamp turns off, turn
the power on again and check the
alarm.
Prolong acceleration time
Decrease the setting value
Eliminate the abrupt change (increase)
Decrease the setting value
Prolong deceleration time
Decrease the setting value
Reduce the load
Increase the capacity of the inverter and motor
Flying start.
Redesign the system so that the motor is not
driven by external force.
Use a brake resistor with a larger capacity.
Prolong the deceleration time (so that GD
the load is met)
Reduce the braking frequency
Increase the brake resistor capacity
Check feedback signal cable and connect
securely.
Set gain frequency properly
(F1402, F1404)
Confirm speed command value or torque
command value
Confirm communication cables are connected
securely
Check the +24V output power supply for load
overloaded
or
conditions
Connect the output cables securely
Check and improve the input power
Confirm output cable and motor insulation
performance
Connect the feedback signal cable securely
Redesign the system so that the motor is not
driven by external force.
Check the fan performance
Contact the supplier
- 196 -
2
of
Actions